3.4
Piping
HRS090 Series
3-28
Connect piping firmly. Incorrect piping might cause leakage of
supplied or drained fluid and wet surrounding area and facility.
Use caution not to allow dust and foreign matter to enter the water
circuit, etc. during connection of piping.
Securely connect the piping at the piping port with specific wrench
when tightening.
Incorrect piping can burst in service.
Use non-corrosive material for fluid contact parts of circulating
fluid and/or facility water. Using the materials that tend to rust or
corrode may cause clogging or/and leakages of the circulating
fluid and facility water circuits. In case of using these kinds of
materials, consider and carry out some prevention against the
rusting or corrosion by the customer side.
Do not generate a rapid change of pressure by water hammer, etc.
Internal parts of the product and/or the piping may be damaged.
Facility water temperature of the facility water outlet port might
rise up to approx.60deg.C.
3.4 Piping
Piping port size
Table 3-12 Piping port size
Name
Port size
1
Recommended
tightening torque
Recommended piping
specification
Circulating fluid supply
Rc1
36 to 38N
・
m
1.0MPa and more
Circulating fluid return
Rc1
36 to 38N
・
m
1.0MPa and more
Drain port
Rc1/4
8 to 12N
・
m
-
Facility water inlet *
1
Rc1/2
28 to 30N
・
m
1.0MPa and more.
(Supply puressure : 0.3 to
0.5MPa)
Facility water outlet *
1
Rc1/2
28 to 30N
・
m
Automatic water-fill port
Rc3/8
22 to 24N
・
m
1.0MPa more
(
Automatic water-fill pressure
0.2 to 0.5MPa
)
Overflow port
Rc3/4
28 to 30N
・
m
Inside diameter 19mm more of
piping
1 : Water cooled type only.
*2 : For Option J [Automatic fluid filling]
[Tips]
<For HRS090-AN-
and
HRS090-WN-
>
A set of thread adapters that converts the connections from Rc to NPT is
enclosed as an accessory. For NPT thread, be sure to use this adapter.
<For HRS090-AF-
and HRS090-WF-
>
A set of thread adapters that converts the connections from Rc to G is
enclosed as an accessory. For G thread, be sure to use this adapter.
Содержание HRS090-A...-20 Series
Страница 8: ...HRX OM T002 Contents HRS090 Series...
Страница 20: ...HRX OM T002 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRS090 Series 2 6...
Страница 64: ...HRX OM T002 Chapter 4 Starting the Product 4 6 Adjustment of Circulating Fluid flow rate HRS090 Series 4 10...
Страница 188: ...HRX OM T002 Chapter 9 Documents 9 9 Daily Check Sheet HRS090 Series 9 16...
Страница 191: ......