HRX-OM- T002
Chapter 7 Alarm Notification and Troubleshooting
HRS090 Series
7.3
Troubleshooting
7-7
Table 7-3 Alarm codes and troubleshooting (3/3)
Code
Alarm name
Alarm
operation*1
(Default
setting)
Cause / Remedy
(Press the reset key after eliminating the
cause.)
AL41
Power stoppage
A.STP
Power supply has been stopped during the
product operation.
Restart the power supply after checking.
AL42
Compressor waiting
A.RUN
Waiting for the compressor to be ready for
operation. Wait for a while.
The alarm will be reset automatically after
starting operation.
AL43
1 Fan failure
P.RUN
Check that there is no power failure such as
ground fault, short circuit, voltage fluctuation,
abnormal interphase voltage, open phase,
surge.
AL45
Compressor
over
current
P.RUN
Check that there is no power failure such as
ground fault, short circuit, voltage fluctuation,
abnormal interphase voltage, open phase,
surge.
Release the compressor thermal trip referring
to [7.3.2 How to release the thermal relay trip
and circuit protector].
AL47
Pump over current
A.STP
Check that there is no power failure such as
ground fault, short circuit, voltage fluctuation,
abnormal interphase voltage, open phase,
surge.
Release the pump thermal trip referring to
[7.3.2 How to release the thermal relay trip
and circuit protector].
AL50
Incorrect phase error
A.STP
The phase of the power line is connected by
incorrect phase.
AL51
Phase
board
over
current
A.STP
Check that there is no power failure such as
ground fault, short circuit, voltage fluctuation,
abnormal interphase voltage, open phase,
surge.
Release the circuit protector trip referring to
[7.3.2 How to release the thermal relay trip
and circuit protector].
*1: Water-cooled type model does not generate this alarm.
Содержание HRS090-A...-20 Series
Страница 8: ...HRX OM T002 Contents HRS090 Series...
Страница 20: ...HRX OM T002 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRS090 Series 2 6...
Страница 64: ...HRX OM T002 Chapter 4 Starting the Product 4 6 Adjustment of Circulating Fluid flow rate HRS090 Series 4 10...
Страница 188: ...HRX OM T002 Chapter 9 Documents 9 9 Daily Check Sheet HRS090 Series 9 16...
Страница 191: ......