HRX-OM-W058
Chapter 8 Control, Inspection and Cleaning
HRS-R Series
8.2
Inspection and Cleaning
8-5
Replacement of circulating fluid
Clean the tank and replace the circulating fluid.
For the circulating fluid, select from the specification range shown in
Quality standard for fresh water (tap water)
When using 15% ethylene glycol solution, check that the concentration is within the
range of 15% +5/-0.
8.2.4
Inspection every 6 months
Check for water leakage from pump (For option T [High pressure pump])
Remove the panel and check the pump for excessive leakage. If the
leakage is found, replace the mechanical seal. Order the mechanical seal
described in “8.3 Consumables” as a service part.
Leakage from the mechanical seal
It is impossible to prevent the leakage from the mechanical seal completely
because of its structure. Although the leakage is described as 3cc/hr or less.
The recommend life time of the mechanical seal before needing replacement is
6000 to 8000 hours (usually 1 year)
Fig. 8-3 Check for water leakage from pump
Check point to see leakage
Содержание HRS018-A
Страница 16: ...HRX OM W058 Chapter 1 Safety Instructions 1 8 Material Safety Data Sheet MSDS HRS R Series 1 10...
Страница 22: ...HRX OM W058 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRS R Series 2 6...
Страница 50: ...HRX OM W058 Chapter 3 Transport and Setting Up 3 7 Wiring of external switch HRS R Series 3 28...
Страница 130: ...HRX OM W058 Chapter 6 Option Optional Accessories 6 5 Option V Stainless steel enclosure HRS R Series 6 4...
Страница 146: ...HRX OM W058 Chapter 8 Control Inspection and Cleaning 8 4 Stop for a Long Time HRS R Series 8 10...
Страница 161: ......