background image

HRX-OM-W002-A 

Chapter 2 Name and Function of Parts

 

HRR Series 

2.3 Function of Parts   

 
 

2-5 

2.3  Function of Parts 

The function of parts is as follows

 

 

Table 2-3

 

  Function of parts

 

Name

 

Name

 

Operation display panel 

Runs and stops the product and performs settings such as the circulating 
fluid temperature.   
For details, refer to 

’’2.4

 Operation display panel

’’

Fluid level gauge 

Indicates the circulating fluid level of the tank. For details, refer to 

’’3.5 

Fill 

of circulating fluid

’’

Power supply switch 

Shuts off the power supply to the internal eqipment of product.

 

Model label 

Shows the part number of the product. 
For details, refer to 

‘’1.4 

Product Label

’’

Circulating fluid outlet port 

The circulating fluid flows out from the outlet port. 

Circulating fluid return port 

The circulating fluid returns to the return port. 

Drain port 

Port to drain the circulating fluid out of the tank.

 

Power supply connector

 

Connect the power cable to the Power supply connector 
accessory, and then plug it in. 
For details, refer to " 3.3.3 

Preparation and wiring of power supply cable

 

".

 

Communication connector 

CN1,CN2 

Use for contact input / output, serial communication. 
For details, refer to "3.3.3 

Preparation and wiring of power supply 

cable

". 

Facility water inlet 

(For water-cooled type) 

A facility water inlet to which the facility water is fed through piping. 
The pressure of facility water should be in a range of 0.3 to 0.5MPa. 

Facility water outlet 

(For water-cooled type) 

A facility water out

let from which the facility water returns to the user’s 

machine through piping. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание HRR012-A*-20 Series

Страница 1: ...lation Operation Original Instructions Thermo chiller HRR012 A 20 HRR018 A 20 HRR024 A 20 HRR030 A 20 HRR012 W 20 HRR018 W 20 HRR024 W 20 HRR030 W 20 Keep this manual available whenever necessary 2018...

Страница 2: ...ion and operation of the product Only people who understand the basic operation of the product through this manual or who perform installation and operation of or have basic knowledge about industrial...

Страница 3: ...ooled refrigerator type 2 1 2 1 2 Water cooled refrigerator type 2 2 2 2 Name and Function of Parts 2 3 2 2 1 HRR A 20 Air cooled type 2 3 2 2 2 HRR W 20 U Water cooled type 2 4 2 3 Function of Parts...

Страница 4: ...set menu 5 11 5 3 9 Information Monitor Setting Menu 5 11 5 4 Basic setting mode 5 12 5 4 1 Screen configuration 5 12 5 4 2 Main menu 5 12 5 4 3 Alarm display menu 5 14 5 4 4 Notice for maintenance Me...

Страница 5: ...nspection every 6 months 8 8 8 3 Stop for a Long Time 8 9 8 3 1 Discharge of the circulating fluid 8 9 8 3 2 Discharge of the facility water Water cooled type 8 12 8 4 Replacement of consumables 8 14...

Страница 6: ...ump capacity 9 14 9 6 1 HRR012 018 024 030 A W 20 9 14 9 6 2 HRR012 018 024 030 A W 20 T 9 14 9 6 3 HRR012 018 024 030 A W 20 MT 9 15 9 7 Required facility water flow for water cooled type 9 15 9 8 Ty...

Страница 7: ...ould read and understand the safety related information in this manual carefully before starting work The safety manager is responsible for strictly observing safety standards but responsibility in re...

Страница 8: ...ding to severity DANGER WARNING CAUTION 1 3 2 Definition of Serious injury and Minor injury Serious injury This term describes injuries that result in after effects including loss of eyesight burns el...

Страница 9: ...needed when contacting an SMC sales distributor How to read the serial number W R 001 April 2018 W R 001 Year Symbol Remarks Month Symbol Remarks Serial no 2018 W Repeat ed from A to Zin alphab etica...

Страница 10: ...or sick condition which might cause an accident Do not remove the panels except for the cases permitted in this manual Do not remove the panels during operation Do not handle this product by any means...

Страница 11: ...ly equipment 1 Turn off the power supply switch on the front of the product to stop the operation of the thermo chiller Fig 1 2 Location of the switch for the power supply 2 Be sure to shut off the br...

Страница 12: ...sal of the product must be handled by a specialized industrial waste disposal agency in accordance with local laws and regulations Only maintenance personnel or qualified people are allowed to open th...

Страница 13: ...1 8 Material Safety Data Sheet MSDS 1 7 1 8 Material Safety Data Sheet MSDS If the material safety data sheets of chemicals used in this product are needed contact an SMC s sales distributor Any chem...

Страница 14: ...HRX OM W002 A Chapter 1 Safety Instructions 1 8 Material Safety Data Sheet MSDS HRR Series 1 8...

Страница 15: ...20 Cooling capacity 012 1000W 1200W 50 60Hz 030 024 2000W 2400W 50 60Hz 2500W 3000W 50 60Hz 018 1600W 1800W 50 60Hz Cooling method Piping thread type Null Rc F G Rc G conversion fitting is included N...

Страница 16: ...fitting is included N NPT Rc NPTconversion fitting is included Option When option D is selected M is selected it becomes DM It is not possible to select only D UL pending Power supply 1 phaseAC200 to...

Страница 17: ...0 Air cooled type Fig 2 3 Names of the parts Table 2 1 Accessory list Operation manual 2 copies English 1 copy Japanese 1 copy Power supply connector 1 pc Maintenance handle for particle filter 1 pc P...

Страница 18: ...type Fig 2 4 Names of the parts Table 2 2 Accessory list Operation manual 2 copies English 1 copy Japanese 1 copy Power supply connector 1 pc Maintenance handle for particle filter 1 pc Particle filte...

Страница 19: ...port The circulating fluid flows out from the outlet port Circulating fluid return port The circulating fluid returns to the return port Drain port Port to drain the circulating fluid out of the tank...

Страница 20: ...tal display section SEC lamp Lights up when seconds are displayed on the digital display section RUN lamp Lights up when the product is started and in operation 4 ALM lamp Lights up when a fault occur...

Страница 21: ...low the instructions shown below for transport Only persons who have sufficient knowledge and experience about the product and system are allowed to transport and set up the product Especially pay att...

Страница 22: ...n microwaves Location that is subjected to potential lightning srtike Location at altitude of 3000m or higher except during product storage and transport Refer to below for details Location where the...

Страница 23: ...ambient temperature than the described value at each altitude 2 Cooling capacity correction coefficient Coefficient to calculate the cooling capacity at each altitude At an altitude of 1800 meters Coo...

Страница 24: ...evel and an air inlet on a wall at a low level Table 3 1 Amount of radiation and required ventilation Model Heat radiation kW Required ventilation amount m3 min Differential temp of 3 C between inside...

Страница 25: ...equired facility water flow rate l min Facility water temprature 25 32 40 HRR012 W 20 Approx 2 5 to 40 Rating 25 8 12 20 HRR018 W 20 Approx 4 12 15 23 HRR024 W 20 Approx 5 14 17 25 HRR030 W 20 Approx...

Страница 26: ...nough space for the ventilation for the product Otherwise it may cause a lack of cooling capacity or and stoppage of the product Ensure there is enough space for maintenance The temperature of the out...

Страница 27: ...vice such as atrailer Mount the product using the fixing holes in the front of the product Use M5 M6 screws bolts or equivalent to the fix the product Do not drag this product after mounting as the fe...

Страница 28: ...nd firmly secured to the product to prevent the external force of cables being applied to the terminals Incomplete wiring or improper securing of wiring may cause electrical shock or excessive heat an...

Страница 29: ...compliant model available as an option HRR 20 U in the UL compliant conditions the conditions shown below must be satisfied Use power supply of overvoltage category 2 transient overvoltage 2500 V or l...

Страница 30: ...cause fire and electric shock Wire with an applicable cable size and terminal Forcibly mounting with an unsuitably size cable may result in heat generation or fire Be sure to lock out and tag out the...

Страница 31: ...ector 4 Connect the other end of the cable to crimped terminals that are connectable to the power supply facility Fig 3 3 Cable connection 5 Insert the power supply connector to the power supply conne...

Страница 32: ...put output communication specification 1 When using the power supply of this product make sure that the total load current is 500 mA or less 2 Refer to 3 3 6 Wiring of contact output signal Item Speci...

Страница 33: ...ntact output signal 1 Output Run status signal N O type 14 Contact output signal 2 Output Remote signal N O type 15 Contact output signal 3 Output Alarm signal N C type Internal circuit 1k 4 7k 1k 4 7...

Страница 34: ...t input signal 1 function selection in Communication setting menu from OFF initial setting value to RN ST Tips This product has two input signals These can be customized depending on the customer s ap...

Страница 35: ...ontact output signal 3 Alarm status signal output N C While alarm being generated Contact open While alarm not being generated Contact closed With power supply shut off Contact open Tips This product...

Страница 36: ...ing of alarm condition can be performed by remote control Refer to Operation Manual Communication Function for more details RS 485 communication connector The following connector is used for this prod...

Страница 37: ...illers for one host computer 31 thermo chillers can be connected at maximum Fig 3 7 Connection of RS 485 Tips Both ends of the communication connection the end nodes need to be connected to the host c...

Страница 38: ...tion connector The following connector is used for this product as RS 232C communication connector Please prepare suitable mating connector Table 3 9 RS 232C communication connector Connector specific...

Страница 39: ...ecurely connect the piping at the piping port with specific wrench when tightening Incorrect piping can burst in service Use non corrosive material for fluid contact parts of circulating fluid and or...

Страница 40: ...ted 2 This product generates an alarm and stops running when the circulating fluid flow rate becomes 3 LPM or less Please make piping that flows more than 3 LPM In addition this product generates an a...

Страница 41: ...3 Pipe hose etc inside diameter 15 or more Thermo chiller Circulating fluid return port Circulating fluid outlet Facillity water outret Water cooled refrigeration Facillity water inlet Water cooled re...

Страница 42: ...which satisfies the water quality standard shown inTable 8 or a 15 aqueous solution of ethylene glycol 4 After filling to the specified level turn the lid clockwise to close Fig 3 11 Fill of circulat...

Страница 43: ...low port regardless of using or not using the automatic water fill function Confirm that the piping to the overflow port is correctly connected Fluid level gauge Confirm that the fluid level is betwee...

Страница 44: ...starts When you operate for the first time after piping the circulating fluid in the tank decreases until the circulating fluid is filled in the piping An alarm occurs when the liquid level falls bel...

Страница 45: ...ter 7 Alarm Notification and Troubleshooting 2 When alarms except those shown above are generated the compressor stops and the circulating fluid pump continues running for a fixed time At this time th...

Страница 46: ...mp stops and the product stops However if the user sets the pump operation time greater than 0s the pump only runs until the circulating fluid discharge temperature reaches a certain value The factory...

Страница 47: ...ing the product Press and hold the RUN STOP key for 1 second RUN lamp goes out and operation stops It takes about 10 seconds of operation to prepare to stop before it stops During the stopping prepara...

Страница 48: ...through the bypass Please note that as the circulating fluid discharge pressure decreases when the valve is opened the display flow rate of this product will decrease Fig 4 6 Adjustment of bypass valv...

Страница 49: ...5 4 4 4 Monitor Menu Displays the temperature of the freezing circuit ambient temperature 5 5 2 5 Standard setting menu Set various setting values such as key lock alarm buzzer sound offset temperatur...

Страница 50: ...imum Alarm display menu Allarm number AL01 Allarm number Alarm number minimum AL02 ALXX MENU AL XXALM Maintenance noti T01 TNN ANT M ENU T02 Basic setting mode 00 circulating fluid return temp 014 Cir...

Страница 51: ...Maintenance notification number Maintenance number maximum Maintenance notification menu Maintenance notification number T01 Maintenance notification number Notification number Minimum TNN ANT M ENU...

Страница 52: ...gerant circuit 000 000 ON MENU MENU REF PRSHI REF PRSLO 212 REF TEMP Ambient temperature Air cooled type only 212 AMB TEMP Advance setting mode 0 0 WRN Contact input signal 2 Delay timer Contact input...

Страница 53: ...nal 1 type Changing of contact input signal 2 detection alarm Contact input signal 1 OFF Detection timer Changing of contact input signal 1 signal detection OUT1 RUN Digital output signal 1 function s...

Страница 54: ...maintenance currently occurring This menu will not be displayed if notice for maintenance has not occurred Upper stage White Lower stage Green TOP screen circulating fluid outlet temperature Present v...

Страница 55: ...on air cooled type Upper stage White Lower stage Green TOP screen MON MENU No 1 screen Temperature of the compressor inlet REF TEMP No 2 screen Ambient temperature 1 AMB TEMP No 3 screen Pressure of h...

Страница 56: ...5 0 EXT HI TMP LIMIT No 13 screen Unused 10 0 EXT LO TMP LIMIT No 14 screen Unused 10 EXT TIME SEC No 15 screen TEMP READY bandwidth upper limit 1 0 0 1 to 9 9 READY H BAND No 16 screen TEMP READY ban...

Страница 57: ...ature drop OFF OFF WRN FLT TEMP OUT LO ALARM No 13 screen Output setting of AL15 circulating fluid temperature drop ON OFF ON TEMP OUT LO OUT P No 14 screen Changing of AL11 Ambient temperature alarm...

Страница 58: ...put signal 2 type ALT ALT MT D IN2 SW TYPE No 11 screen Contact input signal 2 operation A A B D IN2 CON TYPE No 12 screen Contact output signal 1 function RUN 1 D OUT1 SEL No 13 screen Contact output...

Страница 59: ...NO YES DI T RESET No 7 screen Solenoid valve for electric conductivity control Forced OPEN 2 OFF OFF ON DI VALVE 5 5 6 ScreenNo Item Display unit Reference page Upper stage White Lower stage Green TOP...

Страница 60: ...pears when an alarm is generated Circulating fluid temperature setting 2 Press the ENT key the set temperature will blink and the set value can be changed Change the set temperature by pressing the ke...

Страница 61: ...n the digital display Electric conductivity display 6 Press the key The electric conductivity is displayed on the digital display Only for option DM Electric conductivity control function DI water pur...

Страница 62: ...an alarm is occurring the TOP screen of the alarm display menu is displayed When the MENU key is pressed while on the TOP screen of the alarm display menu the next menu screen is displayed Alarm displ...

Страница 63: ...u To reset a notice for maintenance refer to 5 5 6 Reset menu When a notice for maintenance is generated X is displayed on the display panel Table 5 4 1 shows the contents of the notice for maintenanc...

Страница 64: ...he TOP screen of the notice for maintenance menu 2 Press the key Displays the notice for maintenance number currently occurring in order of maintenance notification number 3 Press the key If more than...

Страница 65: ...etting menu Alarm setting menu Communication setting menu Reset menu Information Monitor Menu Alarm history menu 5 5 2 Display contents of monitor menu The following sensor values not displayed in Mai...

Страница 66: ...cooled type Pressure of high pressure refrigerant circuit 4 Press the key Displays pressure of high pressure refrigerant circuit Pressure of low pressure refrigerant circuit 5 Press the key Displays...

Страница 67: ...ration start stop is possible To activate the key lock press the ENT key OFF indication flashes If you press the key while it is flashing it switches to the On display Pressing the ENT key terminates...

Страница 68: ...l the key click sound press the ENT key ON indication flashes Pressing the key while flashing will switch to OFF When the ENT key is pressed the flashing ends and the key click sound turns OFF Alarm b...

Страница 69: ...mmunication is used The circulating fluid temperature sent by serial communication is the circulating fluid temperature which is displayed on the thermo chiller the circulating fluid temperature after...

Страница 70: ...ure OFF Control the temperature so that the discharge temperature of the circulating fluid is circulating fluid temperature set value Example of MODE 1 When the offset temperature is 1 o C the thermo...

Страница 71: ...FF flashes press the key select OFF MD1 MD2 MD3 and confirm with ENT key Offset temperature 7 Press the key Displays offset temperature setting screen To change the offset temperature press the ENT ke...

Страница 72: ...ntrol By pressing the key always OPEN or always CLOSED can be set Selection item Solenoid valve operation CTRL The solenoid valve opens and closes to control the conductivity OPEN Solenoid valve alway...

Страница 73: ...water piping is selected Electric conductivity hysteresis The electric conductivity control hysteresis can be set within a range of 2 0 to 10 0 S cm The initial value is 5 0 S cm For the control imag...

Страница 74: ...lower temperature range Alarms can also be assigned Similar functions include TEMP OUT signal and NOT TEMP READY signal Here is an example showing these relationships TEMP READY function setting examp...

Страница 75: ...red the alarm OFF State Although it is out of band width READY signal continues as READY is out of time State Time when READY disappears after 30 sec has elapsed the READY signal OFF alarm report TEMP...

Страница 76: ...Displays Maximum temperature range of temperature range monitoring function setting screen Temperature range monitoring function When the circulating fluid temperature rises falls alarms AL 14 circul...

Страница 77: ...ture range AL 14 is triggered TEMP OUT output ON State Enter temperature monitoring upper and lower limit range TEMP OUT output OFF State Manual reset of alarm AL 14 cancellation State AL 15 warning i...

Страница 78: ...to ON 11 Temperature range lower limit alarm switching set to WRN 12 Add output of temperature range lower limit alarm Set to ON State An alarm AL 14 is issued when the chiller is activated TEMP OUT...

Страница 79: ...of temperature range monitoring function 22 Press the key Displays Low temperature limit of temperature range monitoring function setting screen For the function refer to P 5 28 Temperature range moni...

Страница 80: ...ust filter replacement time 26 Press the key Displays dust filter replacement time setting screen Dust filter replacement time The maintenance time of the dust filter can be set by the user as a remin...

Страница 81: ...an alarm occurs Alarm setting menu TOP screen 1 When the MENU key is pressed while the Basic setting menu TOP screen is displayed Alarm setting Menu TOP screen is displayed Changing of circulating flu...

Страница 82: ...threshold for this set amount of time AL09 circulating fluid discharge pressure rise alarm is generated The detection time can be set in the range shown below Setting range 0 to 60 sec Initial value 5...

Страница 83: ...tial value 5 sec Setting for electric conductivity rise alarm 8 Press the key Displays screen for setting value of electric conductivity rise alarm threshold Displayed only when Option DM is selected...

Страница 84: ...N Output signal to contact output or serial communication OFF No signal is output Example If the user does not want to generate an alarm but wants a signal for contact output or serial communication w...

Страница 85: ...uid temperature rise occurs Set value Contents Initial value ON Output signal to contact output or serial communication OFF No signal is output Changing of circulating fluid temperature drop alarm beh...

Страница 86: ...r water cooled type Operation for alarm AL11 Ambient temperature alarm can be selected Set value Contents Initial value OFF Alarm is not generated WRN Operation of this product will continue when the...

Страница 87: ...et value Contents Initial value OFF Alarm is not generated WRN Operation of this product will continue when the alarm occurs FLT Operation of this product will stop when the alarm Occurs Switching of...

Страница 88: ...act input signal 1 is not detected When the signal is not detected for the set time the alarm is generated Setting range 0 to 10sec Initial value 0sec Switching of the contact input signal 2 22 Press...

Страница 89: ...the contact input signal 2 is not detected When the signal is not detected for the set time alarm is generated Setting range 0 to 10sec Initial value 0sec Switching of communication error alarm 25 Pr...

Страница 90: ...ion when an alarm is generated Setting range 0 to 9999sec Initial value 0sec Continuation of the pump operation For some alarms the pump can continue to operate even when the alarm is generated by set...

Страница 91: ...er leakage WRN 1 AL04 WATER LEAK AL09 Circulating fluid discharge pressure rise FLT 2 AL09 HIGH PRESS AL10 Flow rate decreased WRN 1 AL10 LOW FLOW WRN AL11 Ambient temperature is out of the range 3 OF...

Страница 92: ...ntenance Alarm AL28 Notice for maintenance is generated Operation for alarm AL28 Notice for maintenance can be selected Set value Contents Initial value OFF Alarm is not generated Only X is displayed...

Страница 93: ...g Menu TOP screen is displayed the display is changed to the top of Communication setting menu Serial protocol 2 Press the key Displays screen for setting the serial protocol Select communication prot...

Страница 94: ...etting the slave address Sets slave address Setting range 1 to 32 Initial value 1 Communication speed 6 Press the key Displays screen for setting the communication speed Selects the communication spee...

Страница 95: ...t input signal 1 Set value Contents Initial value ALT Alternate signal mT Momentary signal Contact input signal 1 Operation 9 Press the key Displays screen for setting the operation of the Contact inp...

Страница 96: ...2 Set value Contents Initial value ALT Alternate signal mT Momentary signal Contact input signal 2 Operation 12 Press the key Displays screen for setting the operation of the Contact input signal 2 S...

Страница 97: ...nal of the contact input signal 2 Selected alarm status signal output Selected notice for maintenance signal output Contact output signal 1 Operation 14 Press the key Displays screen for setting the o...

Страница 98: ...ignal 2 Displays the function for the Contact output signal 2 Set value Explanation Initial value Default setting No output signal Operation status signal output Remote status signal output Unused Rea...

Страница 99: ...L 01 to AL 32 Initial value AL 01 Contact output signal 2 Select maintenance 20 Press the key Displays screen for setting the selected maintenance of the Contact output signal 2 The alarm is valid whe...

Страница 100: ...o be allocated to Contact output signal 3 Setting range AL 01 to AL32 Initial value AL01 Set value Explanation Initial value Default setting No output signal Operation status signal output Remote stat...

Страница 101: ...changed back to the default values Operation time Length of operaton are reset Reset menu TOP screen 1 When the MENU key is pressed while the Communication Setting Menu TOP screen is displayed the di...

Страница 102: ...operation time of the compressor 4 Press the key Displays screen for resetting the operation time of the compressor When the operation time of the compressor is reset the operation time becomes 0 hour...

Страница 103: ...6 Press the key Displays screen for resetting operation time of the dust proof filter Displayed for air cooled type only When the operation time of the dust proof filter is reset the operation time b...

Страница 104: ...en the display is flashing press key and select YES Then press ENT key DI solenoid valve forced open 8 Press the key Displays screen for setting DI solenoid valve Displayed for option DM Electric cond...

Страница 105: ...anged to the Information Monitor Menu TOP screen Product No 2 Press the key Displays Compressor output Refrigeration Type and Thread for piping Power supply Option 3 Press the key Displays Power suppl...

Страница 106: ...mp 8 Press the key Displays accumulated operation time of the pump Operation time is accumulated up to 1 000 000 hour Values are displayed alternately when exceeding 9999 hours Example of display 12 3...

Страница 107: ...re displayed alternately when exceeding 9999 hours Example of display 12 345 hour 1 2345 alternately display Operation time of DI filter 12 Press the key Displays accumulated operation time of the DI...

Страница 108: ...ta address is different 4201 FUNCTION is not supported 0101 Modbus format is different 0081 Slave address is different 0041 CRC is different 0021 LRC is different 0011 Chiller mode is ASCII but custom...

Страница 109: ...ssed while Information Monitor Menu TOP screen is displayed the display is changed to the Alarm History menu TOP screen Press key to display the latest alarm Older alarms are displayed by pressing key...

Страница 110: ...HRX OM W002 A Chapter 5 Display and Setting of Various Functions 5 5 Advanced setting mode HRR Series 5 62...

Страница 111: ...0 to 48 0 S cm Set range of target electric conductivity 5 0 to 45 0 S cm 1 Set range of electric conductivity hysteresis 2 0 to 10 0 S cm 1 Default setting is set to Electric conductivity set value...

Страница 112: ...o Chiller indicates notice for maintenance when driving time is passed a recommended preventive maintenance hours Please contact to service center to ask for maintenance of the pump and mechanical sea...

Страница 113: ...4 1 Option Y With feet and no Rack Mounting bracket Rack mounting brackets are removed as they are not necessary when the product is not mounted in a rack This option has rubber feet for installing th...

Страница 114: ...al should be prepared separately by user Anti quake bracket material stainless thickness 1 5mm Part no Description Qty Applicable model HRR TK001 Anti quake bracket A Anti quake bracket B Nut M8 Bolt...

Страница 115: ...ion for details It is possible to read the alarm status using serial communication Refer to the Operation Manual for communication for details This product makes two type action depend on generated al...

Страница 116: ...ms are generated the alarm codes are displayed one by one by pressing the key Press the MENU key to display the TOP screen of the alarm menu Alarm number Alarm number maximum Alarm number AL01 LO W M...

Страница 117: ...en Press the RESET key The alarm buzzer is stopped Tips The alarm buzzer can be set not to make sound Refer to P 5 19 Alarm buzzer sound The procedure to stop the alarm buzzer is not necessary when th...

Страница 118: ...ow to reset the alarm signal condition after eliminating the cause of the alarm Ensure that the alarm display screen is displayed Alarm can only be reset on this screen Press RESET key The alarm is re...

Страница 119: ...temp FLT AL19 RET TEMP FLT Return temp 45oC or higher Insufficient chiller flow rate overload etc Increase the flow rate through the chiller Adjust the by pass valve AL21 High circulating fluid discha...

Страница 120: ...hing The power supply switch is not turned on Turn on the power supply switch Failure of power supply switch Replace the power supply switch No power supply The breaker for the power supply is not tur...

Страница 121: ...Copper mg L 0 1 or less 0 3 or less Sulfide ion mg L Not detected Not detected Ammonium ion mg L 0 1 or less 1 0 or less Residual chlorine mg L 0 3 or less 0 3 or less Free carbon dioxide mg L 4 0 or...

Страница 122: ...he display should be clear and legible Check the functionality Check that the keys RUN STOP MENU ENT and operate correctly Circulating fluid temperature Check on the operation panel There should be no...

Страница 123: ...generation of smoke There should be no active alarm signal Facility water for water cooled type Check the facility water condition Temperature flow rate and pressure are within the specified range If...

Страница 124: ...entilation port Air cooled type Removal of the dust proof filter 1 The dust proof filter is installed inside of filter panel in front of this product 2 Loosen filter panel holding screws by using cros...

Страница 125: ...fluid Replace the circulating water clean water periodically Ensure that the water has not been contaminated and that there is no algae growth Circulating water inside the tank must be clean and there...

Страница 126: ...e facility water system Water cooled type Clean the customer s facility water system and replace facility water Facility water quality must satisfy the criteria specified in Table 8 1 Quality criteria...

Страница 127: ...arge of the facility Water 2 The strainer is installed on the back of the product Remove the strainer using a tool such as a spanner When removing the strainer product should be fixed to do not move 3...

Страница 128: ...r excessive leakage If the leakage is found replace the mechanical seal Fig 8 2 4 leak check Pump Circulating fluid should not be accumulating in drain pan Leakage from the mechanical seal It is impos...

Страница 129: ...f the circulating fluid for the method of drain the circulating fluid from the product 3 After draining cover the product with vinyl etc and store 8 3 1 Discharge of the circulating fluid 1 Shut off t...

Страница 130: ...come out from drain port and circulating fluid outlet When executing this operation tank cap should be closed and bypass valve should be opened 4 Particle filter is installed inside of this product D...

Страница 131: ...lating fluid may flow out from the case when removing filter case Discharge circulating fluid inside of filter case Do not drop out filter element from inside of filter case during this operation Afte...

Страница 132: ...re that there is no pressure applied inside the piping 3 Remove the piping from facility water inlet outlet port 4 Remove the cover panel on the back of the product using a cross slot screwdriver 4 fi...

Страница 133: ...lug Facility water will come out from facility water inlet port Fig 8 4 Discharge of the facility water 6 After draining the facility water securely tighten the air release plug 7 Install the cover pa...

Страница 134: ...ity control function DI water pure water piping is selected a DI filter is installed inside this product When replacing the DI filter it is necessary to discharge the circulating fluid Wear protective...

Страница 135: ...the OUT side have the same shape Remove the connection fitting on both sides and remove the DI filter 5 Install the DI filter in the reverse procedure that you removed There is no flow direction in t...

Страница 136: ...tion T C3 PM DCPS 1 3 5 PCB2 CN2 1 3 G3 Yellow Green R S C TH Black Black Black 2 4 C2 CM CN1 3 1 2 4 6 7 5 G5 Yellow Green C1 Black Black Black 1 3 7 8 9 6 Black Yellow Green Brown Blue In the device...

Страница 137: ...ate sensor 35 36 34 FL Brown Blue Black 25 26 CN1 2 2 Blue Blue Blue Blue Blue Brown Blue Blue Blue CN7 Brown Blue Brown Blue Brown Blue Blue Blue Blue Blue Blue Blue Blue Blue 1B 2B 3B 7 8 9 10 12 11...

Страница 138: ...HRX OM W002 A Chapter 8 Control Inspection Exchange and Cleaning 8 5 Electrical schematic diagram HRR Series 8 18...

Страница 139: ...ng Heat exchanger 12 Brass 17 SiC Aluminum oxide ceramic Carbon PP PE POM PA FKM EPDM PVC PPS AS fluoropolymer 13 Ion exchange resin 13 Electrical system Power supply 1 phase AC200 to 230V 50 60Hz All...

Страница 140: ...the circulating fluid is not included The weight will increase by 1kg when option DM Electric conductivity control Applicable to deionized water pipimg is selected The weight will increase by 5kg whe...

Страница 141: ...azing Heat exchanger 12 Brass 18 SiC Aluminum oxide ceramic Carbon PP PE POM PA FKM EPDM PVC PPS AS fluoropolymer 13 Ion exchange resin 13 Facility water outlet system Temperature range 5 to 40 Pressu...

Страница 142: ...acket is selected refer to 6 4 Option Y With feet and no Rack Mounting bracket 11 Weight when the circulating fluid is not included The weight will increase by 1kg when option DM Electric conductivity...

Страница 143: ...ed on the IPCC AR4 Revised Fluorocarbons Recovery and Destruction Law Japanese law R134a 1 430 1 430 R404A 3 922 3 920 R407C 1 774 1 770 R410A 2 088 2 090 Note 1 This product is hermetically sealed an...

Страница 144: ...2 Outline dimensions HRR Series 9 6 9 2 Outline dimensions 9 2 1 HRR012 018 A 20 For Option Y With feet and no Rack Mounting bracket refer to 6 4 Option Y With feet and no Rack Mounting bracket Fig 9...

Страница 145: ...ocuments HRR Series 9 2 Outline dimensions 9 7 9 2 2 HRR012 018 W 20 For Option Y With feet and no Rack Mounting bracket refer to 6 4 Option Y With feet and no Rack Mounting bracket Fig 9 2 Outline di...

Страница 146: ...ocuments 9 2 Outline dimensions HRR Series 9 8 9 2 3 HRR024 030 A 20 For Option Y With feet and no Rack Mounting bracket refer to 6 4 Option Y With feet and no Rack Mounting bracket Fig 9 3 Outline di...

Страница 147: ...ocuments HRR Series 9 2 Outline dimensions 9 9 9 2 4 HRR024 030 W 20 For Option Y With feet and no Rack Mounting bracket refer to 6 4 Option Y With feet and no Rack Mounting bracket Fig 9 4 Outline di...

Страница 148: ...et Option D Temp sensor Circulating fluid circuit Refrigerant circuit Electric conductivity circuit For option D Electric conductivity control Comp Expansion 1 Temp sensor Expansion 2 Press sensor Hea...

Страница 149: ...ected 0 500 1000 1500 2000 2500 0 10 20 30 40 Cooling capacity W Circulating fluid temperature 50Hz 25 32 40 Ambient temp or Facility water temp 0 500 1000 1500 2000 2500 0 10 20 30 40 Cooling capacit...

Страница 150: ...0 3500 4000 0 10 20 30 40 Cooling capacity W Circulating fluid temperature 50Hz 25 32 40 Ambient temp or Facility water temp 0 500 1000 1500 2000 2500 3000 3500 4000 0 10 20 30 40 Cooling capacity W C...

Страница 151: ...Heating capacity W Circulating fluid temperature 50Hz 40 32 25 5 Ambient temp or Facility water temp 0 200 400 600 800 0 10 20 30 40 Heating capacity W Circulating fluid temperature 60Hz 40 32 25 5 Am...

Страница 152: ...24 030 A W 20 T Fig 9 14 Pump capacity HRR012 018 024 030 A W 20 T 0 0 0 1 0 2 0 3 0 5 10 15 20 25 Pressure MPa Circulating fluid flow rate L min Outlet 60Hz Outlet 50Hz Allowable operatingrange Retur...

Страница 153: ...he opution with rated circulating fluid cooling capacity which is described in fig 9 4 1 to 9 4 4 Fig 9 16 Required facility water flow for water cooled type 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 5 10 15 20 2...

Страница 154: ...side this product unless you have been trained to do so DO NOT work inside this product unless you have been trained to do so DO NOT work inside this product unless you have been trained to do so DO N...

Страница 155: ...ck and record the condition at start right after setting up Inlet pressure MPa Flow rate L min Temperature Operation conditions Presence of error Present Not present Circulating fluid temp Fluid amoun...

Страница 156: ...HRX OM W002 A Chapter 9 Documents 9 9 Daily Check HRR Series 9 18...

Страница 157: ...s 4 The product was modified or altered in construction 5 The failure was a secondary failure of the product caused by the failure of equipment connected to the product 6 The failure was caused by a n...

Страница 158: ...form checks and maintenance daily checks and regular checks specified in the Operation Manual and Maintenance Manual 3 Record the check and maintenance results on the daily check sheet attached to the...

Страница 159: ......

Страница 160: ...14 1 Sotokanda Chiyoda ku Tokyo 101 0021 JAPAN Tel 81 3 5207 8249 Fax 81 3 5298 5362 URL http www smcworld com Note Specifications are subject to change without prior notice and any obligation on the...

Отзывы: