HRX-OM-X084
Chapter 5
Display and Setting of Various Functions
5.3 List of parameters
HRR Series
5-8
5.3.5 Standard setting menu
Table 5.3-5 Standard setting menu parameter list
1
Can only be set with option DM (Electric conductivity control function, DI water (pure water)
piping).
2
Can only be set with air-cooled type.
Initial value
Select/setting range
TOP
screen
-
SET
-
MENU
-
No.1
screen
Key-lock
OFF
OFF/ON
KEY
⇒
LOCK
-
No.2
screen
Basic setting mode
ON
OFF/ON
EASY
⇒
MODE
-
No.3
screen
Key click sound
ON
OFF/ON
KEY
⇒
CLICK
-
No.4
screen
Alarm buzzer
ON
OFF/ON
ALARM
⇒
BUZZ
-
No.5
screen
Offset mode
OFF
OFF/MD1/MD2/MD3
OFSET
⇒
MODE
-
No.6
screen
Offset temperature
0.0
-20.0 to 20.0
OFSET
⇒
TEMP
℃
No.7
screen
Electric conductivity control *1
Ctrl
Ctrl/OPEN/CLSE
DI
⇒
Ctrl
-
No.8
screen
Electric conductivity
setting value
(
μS/cm
)
*1
25.0
0.5 to 45.0
DI.SP
-
No.9
screen
Electric conductivity
Hysteresis setting value
(
μS/cm
)
*1
5.0
0.1 to 10.0
DI.HYS
-
No.10
screen
Unused
OFF
-
EXT
⇒
Ctrl
-
No.11
screen
Unused
0.0
-
EXT
⇒
OFSET
℃
No.12
screen
Unused
35.0
-
EXT
⇒
HI.TEMP
⇒
LIMIT
℃
No.13
screen
Unused
15.0
-
EXT
⇒
LO.TEMP
⇒
LIMIT
℃
No.14
screen
Unused
10
-
EXT
⇒
TIME
SEC
No.15
screen
TEMP READY bandwidth upper limit
1.0
0.1 to 9.9
READY
⇒
H.BAND
℃
No.16
screen
TEMP READY bandwidth lower limit
-1.0
-9.9 to -0.1
READY
⇒
L.BAND
℃
No.17
screen
TEMP READY stability time
180
10 to 9999
READY
⇒
TIME
SEC
No.18
scree
TEMP READY alarm of monitoring start time
600
0 to 9999
READY
⇒
STAR
T
SEC
No.19
screen
Time TEMP READY remove
5
0 to 600
READY
⇒
READY
SEC
No.20
screen
Upper limit of circulating fluid
temperature monitor
40.0
15.0 to 45.0
TEMP
⇒
OUT
⇒
HI.TEMP
℃
No.21
screen
Lower limit of circulating fluid temperature monitor
5.0
1.0 to 40.0
TEMP
⇒
OUT
⇒
LO.TEMP
℃
No.22
screen
Monitor circulating fluid temperature
rise / drop alarm
rn.st
rn.st/PW.on
TEMP
⇒
OUT
⇒
ALARM
-
No.23
screen
Start time of circulating fluid temperature monitor
600
0 to 9999
TEMP
⇒
OUT
⇒
START
SEC
No.24
screen
circulating fluid temperature monitor is outside
of the time range
5
0 to 600
TEMP
⇒
OUT
⇒
OVER
SEC
No.25
screen
Dust filter replacement time*2
5000
1 to 9999
FLTR
⇒
TIME
H
No.26
screen
DI filter replacement time*1
5000
1 to 9999
DI
⇒
TIME
H
No.27
screen
Temperature control speed
0
-10 to 10
CTRL
⇒
SPEED
-
5.5.3
ScreenNo.
Item
Display unit
Unit
display
Reference
page
Upper stage
(
White
)
Lower stage
(
Green
)
Содержание HRR010-A-10 Series
Страница 14: ...HRX OM X084 Chapter 1 Safety Instructions 1 8 Material Safety Data Sheet MSDS HRR Series 1 8...
Страница 46: ...HRX OM X084 Chapter 3 Transport and Setting Up 3 5 Fill of circulating fluid HRR Series 3 24...
Страница 120: ...HRX OM X084 Chapter 6 Option 6 5 Option Z HRR Series 6 6...
Страница 141: ...HRX OM X084 Chapter 8 Control Inspection Exchange and Cleaning HRR Series 8 4 Replacement of consumables 8 15...
Страница 146: ...HRX OM X084 Chapter 8 Control Inspection Exchange and Cleaning 8 5 Electrical schematic diagram HRR Series 8 20...
Страница 165: ......