Specifications

• Prepare maintenance space.
• Do not drop or bump, or apply excess impact.
• Do not pull the lead wire forcefully, not lift the product by pulling the lead

wire. (Tensile force 49N or less).

• Mount a sensor by observing the proper tightening torque.
• Install or connect the flow sensor so that the flow direction specified on the

label matches with actual flow direction.

• Pipe the flow sensor after eliminating dust in piping by air blow to avoid

failure and malfunction.

• Use dry air which complies with the quality grade of ISO 8573-1 1.1.2 to

1.6.2 : 2001.

• If the entering of foreign material to the fluid is possible, install and pipe the

filter or the mist separator to the inle to avoid failure and malfunction.

• Avoid repeatedly bending or stretching the lead wire.
• Wire correctly.
• Do not wire while the power is supplied.
• Do not wire in conjunction with power lines or high voltage lines.
• Wire as short as possible to avoid the affect of noise and surge.
• Never use in the presence of explosive gases.
• Do not use in an area where magnetic field is generated to avoid

malfunction of sensor.

• Do not operate where the flow sensor is exposed to water.
• Do not use the sensor for poisonous substances, deleterious substances

and corrosive gas. This sensor is not a explosion proof. Do not use for
flammable gas.

• Do not apply heat cycle to the flow sensor.
• Do not used in an area where surges are generated.
• Sensors are not equipped with surge protection against lightening.
• Avoid using sensors in an environment where the likelihood of splashing or

spraying of water, chemicals, and oil to avoid failure and malfunction.

• Consider operating environment according to protection class.
• Do not use the flow sensor where exposed to vibration or impact. Vibration

may interfere correct measurement.

• Flow sensor has to be fixed when used.
• Operation under low temperature (5    or less) leads to cause damage or

operation failure due to frozen moist in the fluid or air.

• Do not short circuit the load.
• Maintenance and inspection should be performed periodically.
• Analog output may fluctuate by 2 to 3% for 5 minutes after supplying power

to the flow sensor.

• Do not poke inside a piping port with a stick.

Dimensions and Names of Individual Parts (unit: mm)

2   M5   0.8  Thread depth 3.8

Piping

1

IN

2

OUT

2      3.4

Mounting

15.2

14

3

0.8

7.1

(15)

10

34.4

18

FLOW SENSOR

2

OUT

FLOW SENSOR

L-type bracket
(Tapped)

(25.7)

10

12

5

2 x 4.5

24

34

20

1

2

9.1

With L-type bracket

Note 1) Converted value of volume flow at ANR (20    , 101.3kPa, 65%R.H.).
Note 2) Analog output shows 3V when flow is zero. Changes to 5V side when flow direction is 

IN     OUT. 1V side when OUT     IN.

Note 3) %F.S. in the table takes 4V (1-5V) as a full scale.
Note 4) 0kPa means release to the atmosphere.
Note 5) Applicable pressure range.
Note 6) Pressure range satisfies product specification.

Model

Measured fluid

Dry air, N

2

(Air quality class is ISO 8573-1 1.1.2 to 1.6.2 : 2001)

Flow rate       

/min

Note1)

(measurement range)

2%F.S. or less

Note3)

Repeatability

2%F.S. or less (0 to 300kPa)

5%F.S. or less (-70 to 0kPa)

Pressure 

characteristic

(0kPa reference

Note4)

)

2% F.S. or less (15 to 35    )

5% F.S. or less (0 to 50    ) 

-100kPa to 400kPa

500kPa

Proof pressure

At voltage output : 1 to 5V

Output impedance : approx. 1k

5ms or less (Response 90%)

Response time

12 to 24VDC     10%, ripple(p-p) 10% or less (Protected against inverse connection)

IP40

Enclosure

0 to 50    (No freezing or condensation)

Operating fluid temp.

0 to 50    (No freezing or condensation)

Operating temp. range

35 to 85%R.H. (No condensation)

Storage humidity range

1000V AC, 1min Between battery and the body

Withstand voltage

50M    or more(500V DC Mega) Between battery and the body

10 to 150Hz 1.5mm amplitude  

98m/s

2

acceleration in X, Y, Z directions  for 2 hours(Power is not supplied)

Vibration resistance

980m/s

2

X, Y, Z directions  3 times for each(Power is not supplied)

Impact resistance

M5   0.8 (tightening torque : 1 to 1.5N•m or less)

Port size

PPS, Si, Au, SUS316, C3604(Electroless nickel plating)

Fluid contact material

3 core vinyl cabtire cable      2.6, 0.15mm

2

, 2m

Lead wire

10g (without lead wire)

Weight

-10 to 60    (No freezing or condensation)

Storage temp. range

16mA or less

Power consumption

Source voltage

-70kPa to 300kPa

Pressure rate

Note5)

Analog output

(Non-linear output)

Insulation resistance

Resistance

Temperature

characteristics

(25    reference)

Operating pressure

range

Note6)

35 to 85%R.H. (No condensation)

Operating humidity range

PFMV505

PFMV530F

PFMV505F

PFMV530

0 to 0.5

-3 to 3

Note2)

-0.5 to 0.5

Note2)

0 to 3

PFMV510

PFMV510F

0 to 1

-1 to 1

Note2)

Model Indication Method

PFM         -      -

Output specification

Type

V5

Remote type sensor

Contents

Model

1

Analog (1 to 5V)

Contents

Model

Measurement flow range

05

Contents

Model

0.0 to 0.5   /min

10
30

0.0 to 1.0   /min
0.0 to 3.0   /min

05F

-0.5 to 0.5   /min

10F

-1.0 to 1.0   /min

30F

-3.0 to 3.0   /min

Operation manual

Nil

N

With Operation manual (in Japanese and English)

Contents

Model

Without Operation manual

Option(Included in the same package)

Nil

A

Without L-type bracket

Contents

Model

With 

2 L-type brackets and 2 mount screws M3 x 15L included for 1station

ZS - 36 - A

L-type bracket  

Stations

2

2 stns

1 stn

1

4

4 stns

5

5 stns

3 stns

2 L-type brackets, 2 mount screws M3 x 25L included

2 L-type brackets, 2 mount screws M3 x 15L included

2 L-type brackets, 2 mount screws M3 x 45L included
2 L-type brackets, 2 mount screws M3 x 55L included

2 L-type brackets, 2 mount screws M3 x 35L included

3

When optional part is needed by part alone, or to be mounted to the manifold,
please order by part number below.

10

34

24

10 x n + 24 (n=1 to 5)

10 x n + 14

2 x 4.5

20

9.1

2

1

OUT

FLOW SENSOR

FLOW SENSOR

FLOW SENSOR

2

OUT

2

OUT

2

L-type bracket
(Through hole)

L-type bracket
(Tapped)

Mount on one side

Mount on both sides