![SMC Networks FieldServer FS-8700-16 BACnet PTP Скачать руководство пользователя страница 9](http://html1.mh-extra.com/html/smc-networks/fieldserver-fs-8700-16-bacnet-ptp/fieldserver-fs-8700-16-bacnet-ptp_driver-manual_1299041009.webp)
BACnet PTP Serial Driver Manual
Page 9 of 34
5.3
Client Side Node Parameters
Section Title
Nodes
Column Title Function
Legal Values
Node_Name
Provide name for Node.
Up to 32 alphanumeric characters
Node_ID
Specify the BACnet Device object instance.
1 - 16777215
Protocol
Specify protocol used.
BACnet_PTP
Port
Specify port.
P1-P2
Retries*
Number of timeouts before the Node goes offline. 0,1,2,
3
Example
// Client Side Nodes
Nodes
Node_Name , Node_ID , Protocol
, Port , Retries
DEV_1
, 1
, BACnet_PTP , P1
, 2
5.4
Map Descriptor Parameters
Column Title
Function
Legal Values
Map_Descriptor_Name
Name of this Map Descriptor. This is used
for Object_Name Property. Refer to
Up to 32 alphanumeric
characters
Data_Array_Name
Name of Data Array where data is to be
stored in the FieldServer.
One of the Data Array names
from
Section
Data_Array_Offset
Starting location in Data Array.
0 to (Data_Array_Length-1) as
specified in
Section
Function
Function of Client Map Descriptor.
Rdbc, Wrbc, Wrbx, Arcs