CONFIGURING THE FIELDSERVER AS A BACNET SERVER
For detailed information on FieldServer configuration, refer to the FieldServer Configuration Manual. The
information that follows describes how to expand upon the factory defaults provided in the configuration
files included with the FieldServer (s
ee “.csv” sample files provided with the FieldServer).
This section documents and describes the parameters necessary for configuring the FieldServer to
communicate with a BACnet PTP Client.
The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to
enable the FieldServer for BACnet communications, the driver independent FieldServer buffers need to
be declared in the “Data Arrays” section, the FieldServer virtual node(s) needs to be declared in the
“Server Side Nodes” section, and the data to be provided to the clients needs to be mapped in the
“Server Side Map Descriptors” section. Details on how to do this can be found below.
NOTE: In the tables below, * indicates an optional parameter, with the bold legal value as default.
6.1
Driver Specific FieldServer Parameters
Section Title
Bridge
Column Title
Function
Legal Values
Title
FieldServer name.
Text
Network_Number*
Specify a unique network number if there are multiple virtual
Server nodes. Refer to
1-65535
5
Example
// FieldServer Driver specific parameters
Bridge
Title
BACnet Server
6.2
Server Side Connection Parameters
Section Title
Connections
Column Title
Function
Legal Values
Port
Specify which port the device is connected to the
FieldServer.
P1-P2
Baud*
Specify baud rate.
110; 300; 600; 1200; 2400;
4800;
9600
; 19200; 38400;
57600; 115000
Parity*
Specify parity.
None,
Odd, Even
Data_Bits*
Specify data bits.
7
, 8
Stop_Bits*
Specify stop bits.
1
, 2
Protocol
Specify protocol used.
BACnet_PTP
Reliability_Option*
The Reliability_Option parameter selects the rules
by which the BACnet Server determines the
Reliability property of a BACnet object whose
present value is read from a Remote Server Node.
Refer to
Track_Object_Status,
Track_Node_Status,
Always_Reliable