Parameter Setting
The EX600 parameters can be configured for the system, each unit and each channel. Parameters can be
changed by Web server.
■
Parameter definition and setting
With EX600 series, parameters can be set for each unit.
The table below shows settable parameters for the SI unit and input/output units.
•SI unit parameters (1)
No.
Parameter
Definition
Item
Content
Default
setting
Parameter
setting range
1
Hold/Clear
priority setting
Switch the setting
of the output during
communication
error or
communication
idling to follow the
setting of the SI
unit or the
parameters.
Via switch
Setting by SI unit switch
becomes valid.
OFF/Hold can be set
output of all.
○
System
Via software
Setting by EtherNet/IP
TM
object or the Web server
becomes valid.
OFF/Hold/Forced ON can
be set per channel.
2
Short Circuit
Detection
Generates error
when the short
circuit of the valve
is detected.
Enable
Generates an error.
○
Unit
Disable
Does not generate an
error.
3
Restart after
short circuit
Restore the setting
of short circuit
detection error
after the valve
short circuit is
cleared.
Auto
Error is automatically
cleared when the short
circuit is fixed.
○
Unit
Manual
Even when the short
circuit is fixed, error is not
cleared until the power is
supplied again.
4
Open Circuit
Detection
Generates error
when the
disconnection of
the valve is
detected.
Enable
Generates an error.
Channel
Disable
Does not generate an
error.
○
5
Output setting
during
communication
fault
1
Sets output when
communication
error is occurred.
Clear
Turn off the output
○
Channel
Hold
Hold the output
ForceON
Turn on the output
forcefully
6
Output setting
during
communication
idling
1
2
Output setting at
the time of
communication
idling
Clear
Turn off the output
○
Channel
Hold
Hold the output
ForceON
Turn on the output
forcefully