16-
3.4.1.
Pressure P1 (Index 64)
Table 3-9. Pressure P1
Sub
index
Size
[byte]
Acc
ess
Default
(dec)
Content
Description
1
2
R/W
0x0258
(600)
Vacuum confirmation
threshold (P1) of CH0
Set vacuum confirmation threshold (P1) for each
CH. Refer to
Settable range : 11...989 (-1.1 kPa...-98.9 kPa)
Combination conditions with other parameters :
H1+1 ≤ P1 ≤ P2-H2
...
...
...
...
...
16
2
R/W
0x0258
(600)
Vacuum confirmation
threshold (P1) of CH15
3.4.2.
Hysteresis H1 (Index 65)
Table 3-10. Hysteresis H1
Sub
index
Size
[byte]
Acc
ess
Default
(dec)
Content
Description
1
2
R/W
0x0032
(50)
Vacuum confirmation
hysteresis (H1) of CH0
Set vacuum confirmation hysteresis (H1) for each
CH. Refer to
Settable range : 10...988 (1.0 kPa...98.8 kPa)
Combination conditions with other parameters :
10 ≤ H1 ≤ P1-1
...
...
...
...
...
16
2
R/W
0x0032
(50)
Vacuum confirmation
hysteresis (H1) of CH15
3.4.3.
Pressure P2 (Index 66)
Table 3-11. Pressure P2
Sub
index
Size
[byte]
Acc
ess
Default
(dec)
Content
Description
1
2
R/W
0x02EE
(750)
Energy saving operation
threshold (P2) of CH0
Set energy saving operation threshold (P2) for
each CH. Refer to
Settable range : 21...999 (-2.1 kPa...-99.9 kPa)
Combination conditions with other parameters :
P1+H2 ≤ P1 ≤ 999
...
...
...
...
...
16
2
R/W
0x02EE
(750)
Energy saving operation
threshold (P2) of CH15
3.4.4.
Hysteresis H2 (Index 67)
Table 3-12. Hysteresis H2
Sub
index
Size
[byte]
Acc
ess
Default
(dec)
Content
Description
1
2
R/W
0x0064
(100)
Energy saving operation
hysteresis (H2) of CH0
Set energy saving operation hysteresis (H2) for
each CH. Refer to
Settable range : 10...988 (1.0 kPa...98.8 kPa)
Combination conditions with other parameters :
10 ≤ H2 ≤ P2-P1
...
...
...
...
...
16
2
R/W
0x0064
(100)
Energy saving operation
hysteresis (H2) of CH15