-88-
No.PF
※※
-OMA1007
■
[F98] Setting of output check
By forcibly switching the output ON/OFF operation using the button operation, the operation of the system
can be checked regardless of the measured value. This function can be checked on Byte20 for Base type
or Byte10 for Remote type, please refer to the IO map.
<Operation>
Display [F98] by pressing the UP or DOWN button in function selection mode.
Press the SET button.
Move on to select output check.
Select output check
Press the UP or DOWN button to select the output check.
Move on to flow rate unit bit check.
Flow rate unit bit check
Select the flow rate unit bit check by
pressing the UP or DOWN button.
Press the SET button to set.
Flow rate criteria bit check
Select the flow rate criteria bit check by
pressing the UP or DOWN button.
Press the SET button to set.
[F] (Forced output) is selected
Press the SET button to set.
[n] (Normal output) is
selected.
Press the SET button
to set.
Return to function
selection mode.
Move on to flow rate criteria bit
check.
Move on to flow rate diagnosis bit
check.