[F30] Setting of accumulated value hold
In the default setting, the accumulated flow value is not held when the power supply is turned off.
This function enables the accumulated flow value to be stored in permanent memory every 2 or 5 minutes.
∗
: When using the accumulated value hold function, calculate the product life from the operating conditions, and use the product within
its life. Maximum updating time of the accumulated value is 1.5 million times.
If the product is operated 24 hours per day, the product life will be as follows.
•Data memorized every 5 minutes: 5 minutes x 1.5 million times = 7.5 million minutes = 14.3 years
•Data memorized every 2 minutes: 2 minutes x 1.5 million times = 3 million minutes = 5.7 years
If the Accumulated Flow External Reset is repeatedly used, the product life will be shorter than calculated life.
<Operation>
Display [F30] by pressing the UP or DOWN button in function selection mode.
Press the SET button.
Move on to select accumulated value hold.
Select accumulated value hold
Press the UP or DOWN button to select the accumulate value hold.
Press the SET button to set.
Return to function selection mode.
[F30] Setting of accumulated value hold completed
∗
: The value is stored in memory every 2 or 5 minutes. If the power supply is turned off, the accumulated flow since the last time it
was stored will be lost.
∗
: When the power supply is turned on again, the accumulated flow count will start from the last value recorded at B.
Содержание AMS20
Страница 1: ...No PF OMA1007 PRODUCT NAME Air Management System MODEL Series Product Number AMS20 AMS30 AMS40 AMS60...
Страница 13: ...12 No PF OMA1007 Model Indication and How to Order Air Management System Standby E P regulator type...
Страница 14: ...13 No PF OMA1007 Air Management System Standby regulator type...
Страница 40: ...39 No PF OMA1007...
Страница 124: ...123 No PF OMA1007 EXA1 60 PN EN...
Страница 126: ...125 No PF OMA1007 EXA1 60 SA Refer to separate operation manuals for other AMS components...