The honeycomb mesh cover are made in the following series of types according to their width*
B
of the damper
B
of the mesh cover
B
of the damper
B
of the mesh cover
200-250
570
701-750
1070
251-300
620
751-800
1120
301-350
670
801-850
1170
351-400
720
851-900
1220
401-450
770
901-950
1270
451-500
820
951-1000
1320
501-550
870
1001-1050
1370
551-600
920
1051-1100
1420
601-650
970
1101-1150
1470
651-700
1020
1151-1200
1520
* In a special version, the honeycomb mesh cover can be made with dimensions different from the typical ones.
7.
CONDITIONS OF TRANSPORT AND STORAGE
WKP-O should be stored in cardboard boxes and/or on pallets. WKP-O should have a pre-protected actuator cardboard
box. Fire dampers should be stored indoors, providing protection against atmospheric agents, at a minimum
temperature of +5°C.
Do not allow mechanical damage of damper, that may be caused e.g. blows or dropping.
During the transport the dampers should be package in cardboard, and/or put on a pallets and should be secured
before relocating, and against weather conditions. Be especially careful particularly with the WKP-O-E-T type dampers.
After each transport, visual inspection of each fire damper must be carried out.
8.
INSTALLATION TECHNOLOGY
Before installing the fire dampers, make sure that there are no damage, during transport or storage, that could block
the baffle.
Check that the baffle can be opened and closed (full opening and closing position). To open fire dampers WKP-O use
the actuator key.
The opening and closing must proceed smoothly (not stepwise).
Do not pull by baffle to open or close fire damper, it may cause permanent damage, not covered by the warranty.
Before installation verify dimensions of the gap between bottom blade and inside part of the housing under the blade,
and between top blade and inside part of housing above blade. The dimension of the gap cannot be lower than 4 mm.
Before installing, secure the fire damper, by dust and dirt, using a foil or other screening material. It can prevent
components of fire damper by damage.
Dampers to preserve of the declared resistance, insulation and smoke leakage EIS120, EIS90, should be installed on
wall, which was classified as EIS120, EIS90.
It is allowed to install WKP-O dampers in wall with other fire-resistance, should be remembered that fire-resistance in
this situation is resistance of lowest classified (in this regard) element in this system.
Ducts made of flammable and non-flammable materials can be connected to the damper. Ducts should be installed
that they cannot load the damper during fire. Ducts lengthening during fire can be compensated by support and knee.
ATTENTION: Distance between fire dampers or fire damper and construction elements must be compatible with
standard 1366-2:
a.
Minimal 200 mm between fire damper, which are installed in different ventilating wires,
b.
Minimal 75 mm between fire damper and construction element (wall/ceiling).
Содержание WKP-O
Страница 1: ...a Technical Documentation WKP O Fire damper rectangular v https www smay eu ...
Страница 11: ...Version 6 00 Date of editing 16 09 2022 r Page 10 z 27 Technical documentation WKP O Technical data BFN230 T ...
Страница 12: ...Version 6 00 Date of editing 16 09 2022 r Page 11 z 27 Technical documentation WKP O Technical data BFN24 T ...
Страница 13: ...Version 6 00 Date of editing 16 09 2022 r Page 12 z 27 Technical documentation WKP O Technical data BF230 T ...
Страница 14: ...Version 6 00 Date of editing 16 09 2022 r Page 13 z 27 Technical documentation WKP O Technical data BF24 T ...