Version 6.00
Date of editing:
16.09.2022
r.
Page 7 z 11
Installation manual
WKP-O
III.
INSTALLATION TECHNOLOGY
–
STRUCTURES THICKER THAN 125 mm
In rigid walls, with thickness less than or equal to 125 mm, WKP-O fire dampers are installed in this way that an axis
of the fire baffle matches the axis of the wall, and ensure a concentricity of fire damper and installation opening.
In case when wall have more than 125 mm thickness: WKP-O fire dampers are installed in this way that the damper
border is flush with the wall surface (Fig. 6).
Figure 6. Installation method of fire dampers WKP-O in structures thicker than 125 mm