Version 6.00
Date of editing: 16.09.2022
r.
Page 30 of 30
Technical documentation
KWP-L
Table 6. Diagnostic card
Diagnostic card
No.
Symptoms of
malfunction
Causes of malfunction
How to remove malfunction
1
No signaling
opening/closing fire
damper
1. Failure to fully open the
baffle (wrong connected
ventilation duct)
2. Improperly connected wires
of limit switch
3. Damaged actuator
1. Removing the cause of
blocking baffle
2. Correct wiring
3 . Replacing the actuator
with a new one (after
consulting with fire
damper`s manufacturer)
2
No actuator response
after connecting
power
1 .Damaged actuator
2. Damaged temperature
sensor
3. Locked baffle
1. Replacing the actuator
with a new one (after
consulting with fire
damper`s manufacturer)
2. Replacing the
temperature sensor to a new
one
3 .Removing the cause of
blocking baffle
3
No possibility of
opening the fire
damper with actuator
by key
1 .Broken mechanism in the
actuator (too rapid rotation)
2.Locked baffle
1. Replacing the actuator
with a new one (after
consulting with fire
damper`s manufacturer)
2. Removing the cause of
blocking baffle
9.
TERMS OF WARRANTY
f.
The manufacturer provides guarantee for the delivered product for a period of 24 moths from the date of sale or
another period agreed in the contract. There is a possibility of extending the guarantee, provided that a
separate Maintenance and Service Agreement is signed between the manufacturer and the owner/manager of
the facility.
g.
The basis for complaint handling is to file a complaint within the warranty period, within 7 days of the detect
being discovered. Make the product available in the state in which it appeared to be defective, together with a
detailed description of the technical problem and documents confirming the performance of any inspection
provided by the manufacturer and periodic maintenance.
h.
The manufacturer undertakes to remove the defect within 2 working days of receiving the notification. The
manufacturer undertakes to remove the defect within 21 working days from the date of receipt of the
application together with the complete set of documents, and in the case of necessity to bring in hard-to-reach
materials or parts, the repair will be carried out within the shortest technically reasonable time.
i.
The warranty period is extended by the duration of the repair.
j.
The warranty is valid in the cases described in the OWG.
k.
OWG & OWS documents are available on the website
www.smay.pl
l.
Above terms of warranty apply only in Poland.
Содержание KWP-L
Страница 1: ...a Technical Documentation KWP L Fire Damper rectangular v https www smay eu ...
Страница 14: ...Version 6 00 Date of editing 16 09 2022 r Page 13 of 30 Technical documentation KWP L Technical data BF230 TN ...
Страница 15: ...Version 6 00 Date of editing 16 09 2022 r Page 14 of 30 Technical documentation KWP L Technical data BF24 TN ...