Operation and 

Maintenance Manual 

iSWAY 

Compact pressurization 
unit 

Содержание iSWAY

Страница 1: ...a v https www smay eu Operation and Maintenance Manual iSWAY Compact pressurization unit ...

Страница 2: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 2 6 7 7 10 Intended use 10 10 14 14 16 16 18 18 21 21 25 25 26 26 27 27 29 30 30 31 31 34 35 37 37 37 ...

Страница 3: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 3 38 39 39 39 40 40 41 41 42 43 44 45 45 45 47 50 50 51 54 54 55 57 58 59 60 60 61 62 64 65 67 76 76 82 ...

Страница 4: ...ts Version 2 1 of 3 2022 4 83 88 92 96 1 1 1 Main power supply connection 96 2 1 1 SzA FCK connection 96 3 1 1 Wiring block diagram 98 100 102 102 103 108 108 109 109 110 111 Frequency inverter 113 114 114 116 118 127 128 129 130 130 132 134 138 141 142 145 ...

Страница 5: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 5 155 159 165 165 165 167 167 168 168 169 170 175 175 177 177 177 178 ...

Страница 6: ...nce must be carried out in accordance with the directives and regulations in force in the country where the appliance is installed It is recommended to use the assistance of SMAY Authorised Service Centres during assembly installation commissioning repair and maintenance The documentation should always be kept close to the unit and easily accessible to service personnel ...

Страница 7: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 7 ...

Страница 8: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 8 ...

Страница 9: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 9 ...

Страница 10: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 10 Intended use ...

Страница 11: ...in the protected space Protected space type staircase fire vestibule escape corridor Current shunt Surrounding pressure measuring point reference Static pressure measuring point in the protected space Current shunt Protected space type staircase fire vestibule escape corridor Measuring point of disposition compression rate SRC damper with actuator PZ box MacDmin ...

Страница 12: ...t reference Static pressure measuring point in the protected space Current shunt Protected space type staircase fire vestibule escape corridor Protected space type staircase fire vestibule escape corridor Current shunt Static pressure measuring point in the protected space Surrounding pressure measuring point reference ...

Страница 13: ...al DTR iSWAY Set of products Version 2 1 of 3 2022 13 Surrounding pressure measuring point reference Static pressure measuring point in the protected space Current shunt Protected space type staircase fire vestibule escape corridor ...

Страница 14: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 14 ...

Страница 15: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 15 Detail A ...

Страница 16: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 16 ...

Страница 17: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 17 ...

Страница 18: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 18 Air flow direction intake iSWAY FC Air flow direction outlet iSWAY FC ...

Страница 19: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 19 Auxiliary intake damper Main intake damper Air flow direction Recommended 12 meters ...

Страница 20: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 20 Detail A Detail A ...

Страница 21: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 21 Air flow direction ...

Страница 22: ...anual DTR iSWAY Set of products Version 2 1 of 3 2022 22 TR1 coupling iSWAY ventilator assembly SCR D damper PDA roof base Duct length 1000 mm TR3 coupling iSWAY ventilator assembly SCR D damper PDA roof base Duct length 1000 mm ...

Страница 23: ...SWAY RFC 3 0 and 4 0 1660 320 iSWAY RFC 5 5 and 7 5 2135 320 iSWAY RFC version H1 mm H2 mm iSWAY RFC 1 5 and 2 2 1135 220 iSWAY RFC 3 0 and 4 0 1455 320 iSWAY RFC 5 5 and 7 5 1835 320 TR6 coupling iSWAY ventilator assembly SCR D damper PDA roof base Duct length 1000 mm CPDP roof air intake iSWAY ventilator assembly SCR D damper PDA roof base Duct length 1000 mm ...

Страница 24: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 24 Straight section of the duct length min 400 Ventilator assembly SCR D damper ZS intake louver ...

Страница 25: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 25 CDH K air intake Straight section of the duct length min 400 Ventilator assembly Duct with smoke detector KCD ...

Страница 26: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 26 o o o Air flow direction intake iSWAY FC Air flow direction outlet iSWAY FC ...

Страница 27: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 27 ...

Страница 28: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 28 Auxiliary intake damper Air flow direction Main intake damper Recommended 12 meters ...

Страница 29: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 29 iSWAY FC B H mm mm 0 770 770 1 1000 1005 2 1200 1205 actuator Electric box actuator box damper cable gland ...

Страница 30: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 30 ...

Страница 31: ...WAY Set of products Version 2 1 of 3 2022 31 Standing in the direction of air flow in the supply air unit the operation side is on the right hand Standing in the direction of air flow in the supply air unit the operation side is on the left ...

Страница 32: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 32 ...

Страница 33: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 33 ...

Страница 34: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 34 ...

Страница 35: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 35 ...

Страница 36: ...Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 36 iSWAY RFC type Dimensions A B C D mm iSWAY RFC 1 5 680 iSWAY RFC 2 2 760 iSWAY RFC 3 0 925 iSWAY RFC 4 0 925 iSWAY RFC 5 5 1150 iSWAY RFC 7 5 1150 ...

Страница 37: ...al DTR iSWAY Set of products Version 2 1 of 3 2022 37 A B C D1 D2 W1 W2 mm mm mm mm mm mm mm Unit size 0 1520 1070 870 435 435 770x770 770x770 1 1620 1320 1100 550 550 1000x1000 1000x1000 2 1720 1520 1300 650 650 1200x1200 1200x1200 ...

Страница 38: ...0 350 350 350 350 350 350 Capacity m3 h ARC 17 000 20 000 24 000 31 000 39 000 47 000 Available compression ratio Pa ARC 310 310 290 350 360 320 Weight with AFC kg 219 232 320 331 352 501 527 571 Weight with ARC kg 351 347 357 424 489 503 Weight with AJF kg 203 229 309 319 332 412 487 515 565 Operating temperature C from 25 to 55 with no accessories Type Supply voltage Active power Apparent power ...

Страница 39: ...165 iSWAY WFC 1 5 1035 785 165 iSWAY WFC 2 2 1135 960 185 iSWAY WFC 3 0 1240 960 315 iSWAY WFC 5 5 1355 1135 345 Type 1 1 1 5 2 2 3 0 5 5 Airflow m3 h 9 500 12 700 17 000 27 000 42 000 Available compression ratio Pa 150 150 150 200 200 Total weight kg 66 70 80 110 180 Operating temperature C from 25 to 55 Mounting hole in the wall ...

Страница 40: ...oltage Active power Apparent power V kW kVA 1 1 3x400 2 02 2 06 1 5 3x400 2 50 2 54 2 2 3x400 3 20 3 26 3 0 3x400 4 14 4 22 5 5 3x400 7 09 7 23 iSWAY RFC version A mm B mm C mm D mm iSWAY RFC 1 5 680 142 5 387 559 iSWAY RFC 2 2 760 152 5 442 633 iSWAY RFC 3 0 925 187 5 463 801 iSWAY RFC 4 0 925 187 5 469 801 ...

Страница 41: ...irflow m3 h 10 000 12 000 20 000 25 000 36 000 40 000 Available compression ratio Pa 200 250 250 250 250 250 Total weight kg 100 120 140 160 210 215 Operating temperature C from 25 to 55 according to Fig 9 6 Type Supply voltage Active power Apparent power V kW kVA 1 5 3x400 2 52 2 57 2 2 3x400 3 34 3 40 3 0 3x400 4 11 4 19 4 0 3x400 5 25 5 36 5 5 3x400 6 93 7 07 7 5 3x400 9 19 9 37 ...

Страница 42: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 42 ...

Страница 43: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 43 ...

Страница 44: ... 2 1 of 3 2022 44 Ł type angular corners plastic film wrapped Plastic film wrapped CDH K intake placed into the KT and film wrapped together Plastic film wrapped ventilator placed into the KT and film wrapped together Fasten with the use of a tape along with a pallet ...

Страница 45: ...peration and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 45 Installation direction Axes of flexible connector Air flow direction intake iSWAY FC Air flow direction output iSWAY FC ...

Страница 46: ...ation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 46 Unit size A B C D W2 mm mm mm mm mm 0 2292 1597 1270 435 770x770 1 2506 1847 1500 550 1000x1000 2 2714 2047 1700 650 1200x1200 ...

Страница 47: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 47 Key M 25 View A ...

Страница 48: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 48 Rubber matt ...

Страница 49: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 49 ...

Страница 50: ...ration and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 50 The foundation frame or steel structure used as the supporting structure of the unit must be flat and levelled Service side ...

Страница 51: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 51 1 iSWAY 2 Ground wire 3 Flexible joint 4 Ventilation duct Detail A ...

Страница 52: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 52 wall 1 screw and dowel telescopic duct 2 self drilling screw Hat profile Self drilling screw ...

Страница 53: ...Manual DTR iSWAY Set of products Version 2 1 of 3 2022 53 Wall 5 5 sheet metal screw 10x10 PES gasket Telescopic duct CDH K intake 4 5x19 self drilling screw 10x4 PES gasket Panel Ventilator gasket Vibration absorber Ventilator ...

Страница 54: ...tenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 54 PDA roof base Farmer screw wit dowel Concrete plinth DETAIL A PDA roof base Farmer screw with dowel Brickwork plinth Detail A Screw M8 Nut M8 Washer Ø8 A ...

Страница 55: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 55 ...

Страница 56: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 56 Vertical profile Horizontal profile Reinforcing rib Foot Rectangular channel Hexagonal bolt washer nut RESTAL assembly ...

Страница 57: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 57 SzA FCK 600x750x210 mm cabinet ...

Страница 58: ...tenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 58 Ø6 mm impulse tube in a Ø18 mm corrugated pipe Ø6 mm impulse tube in a Ø18 mm corrugated pipe SCAME 100x100 type box Pressure measuring points in the duct ...

Страница 59: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 59 ...

Страница 60: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 60 ...

Страница 61: ...Set of products Version 2 1 of 3 2022 61 The device Breaker type iSWAY FC 0 3 4G25 92 PKS6 iSWAY RFC WFC device iSWAY FC device Service switch GUARANTEED POWER SUPPLY 3X400V FROM THE SUBSTATION GUARANTEED POWER SUPPLY 3X400V FROM THE SUBSTATION ...

Страница 62: ... DTR iSWAY Set of products Version 2 1 of 3 2022 62 iSWAY FC 0 12 4G25 92 PKS6 iSWAY FC 1 17 4G25 92 PKS6 iSWAY FC 1 20 4G25 92 PKS6 iSWAY FC 1 24 P3 63 iSWAY FC 2 31 P3 63 iSWAY FC 2 39 P3 63 iSWAY FC 2 47 P3 100 iSWAY FC 2 75 P3 100 ...

Страница 63: ... SzA FCK cabinet PZSC connection box Ventilator motor Shut off damper CDH K intake Smoke detector Actuator cable CABLES DESCRIPTION MARK CABLE SORT CABLE TYPE DESIGNATION CABLE SORT CABLE TYPE C NHXCH FE180 PH90 4XDIAMETER DEPENDING ON THE CAPACITY F1 HTKSH FE180 PH90 2x2x1 0 G1 HTKSH FE180 PH90 3x2x0 8 ...

Страница 64: ...RIPTION DESIGNATION CABLE SORT CABLE TYPE C NHXCH FE180 PH90 4XDIAMETER DEPENDING ON THE CAPACITY F1 HTKSH FE180 PH90 2x2x1 0 G1 HTKSH FE180 PH90 3x2x0 8 Frequency inverter SzA FCK cabinet PZWM or PZWD connection box Ventilator motor Shut off damper SRC D CDH K Smoke detector PZS connection box ...

Страница 65: ...x400 17 40 17 75 B 40A gG 50A NHXH FE180 PH90 5x161 2 75 3x400 21 26 21 34 B 50A gG 63A NHXH FE180 PH90 5x161 Type Supply voltage Active power Apparent power Protection on the device Suggested protection in the main switchboard Suggested power cables for the device VAC kW kVA Type A Type 1 1 3x400 2 02 2 06 B 6A gG 10A NHXH FE180 PH90 5x2 51 1 5 3x400 2 50 2 54 B 6A gG 16A NHXH FE180 PH90 5x2 51 2...

Страница 66: ...tage Active power Apparent power Protection on the device Suggested protection in the main switchboard Suggested power cables for the device VAC W VA Type A Type TSS 1 1x230 16 20 1 25 delayed B6 NHXH FE180 PH90 3x1 52 TSS 2 1x230 16 20 1 25 delayed B6 NHXH FE180 PH90 3x1 52 TSS 3 1x230 16 20 1 25 delayed B6 NHXH FE180 PH90 3x1 52 TS X TS X YR 1x230 16 20 1 25 delayed B6 NHXH FE180 PH90 3x1 52 Pow...

Страница 67: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 67 P MACF 24 2 2 HDGs FE180 PH90 3x1 0 T MACF 24 1 2 Powered by Local FireBus ...

Страница 68: ...om WIRING Designation on the diagram Automation elements connections Cable type A1 Guaranteed power supply cable 3x400V for iSWAY FC WFC RFC NHXH FE180 PH90 5x cross section B1 Guaranteed power supply 1x230VAC MSPU TS TSS NHXH FE180 PH90 3x1 5 C1 Control power supply cable 24 VDC double intake HDGs FE180 PH90 3x1 5 D2 Global FireBus bus loop HTKSH FE180 PH90 ekw 2x2x0 8 E2 Cables ALARM SAP NC Oper...

Страница 69: ...RFC NHXH FE180 PH90 5x cross section A2 Ventilator power supply 3x400V for iSWAY FC WFC RFC NHXCH FE180 PH90 4x cross section B1 Guaranteed power supply 1x230VAC MSPU TS TSS NHXH FE180 PH90 3x1 5 C1 Control power supply cable 24 VDC double intake HDGs FE180 PH90 3x1 5 D2 Global FireBus bus loop HTKSH FE180 PH90 ekw 2x2x0 8 E2 Cables ALARM SAP NC Operation confirmation NO Collective failure NC HTKS...

Страница 70: ...S NHXH FE180 PH90 3x1 5 C1 Control power supply cable 24 VDC double intake HDGs FE180 PH90 3x1 5 D2 Global FirsBus bus loop HTKSH FE180 PH90 ekw 2x2x0 8 E2 Cables ALARM SAP NC Operation confirmation NO Collective failure NC HTKSH FE180 PH90 3x2x0 8 F1 Control power supply cable 24 VDC shut off damper HTKSH FE180 PH90 2x2x1 0 G1 Power supply alarm failure smoke detector signal cable HTKSH FE180 PH9...

Страница 71: ...80 PH90 3x1 5 C1 Control power supply cable 24 VDC double intake HDGs FE180 PH90 3x1 5 D2 Global FirsBus bus loop HTKSH FE180 PH90 ekw 2x2x0 8 E2 Cables ALARM SAP NC Operation confirmation NO Collective failure NC HTKSH FE180 PH90 3x2x0 8 F1 Control power supply cable 24 VDC shut off damper HTKSH FE180 PH90 2x2x1 0 G1 Power supply alarm failure smoke detector signal cable HTKSH FE180 PH90 3x2x0 8 ...

Страница 72: ...tem WIRING Designation on the diagram Automation elements connections Cable type A1 Guaranteed power supply cable 3x400V for iSWAY FC WFC RFC NHXH FE180 PH90 5x cross section C1 Control power supply cable 24 VDC double intake HDGs FE180 PH90 3x1 5 C8 Guaranteed power supply cable TSS X 24 VDC HDGs FE180 PH90 3x2 5 D2 Global FirsBus bus loop HTKSH FE180 PH90 ekw 2x2x0 8 E2 Cables ALARM SAP NC Opera...

Страница 73: ... RFC NHXH FE180 PH90 5x cross section A2 Ventilator power supply 3x400V for iSWAY FC WFC RFC NHXCH FE180 PH90 4x cross section C1 Control power supply cable 24 VDC double intake HDGs FE180 PH90 3x1 5 C8 Guaranteed power supply cable TSS X 24 VDC HDGs FE180 PH90 3x2 5 D2 Global FireBus bus loop HTKSH FE180 PH90 ekw 2x2x0 8 E2 Cables ALARM SAP NC Operation confirmation NO Collective failure NC HTKSH...

Страница 74: ...iSWAY FC WFC RFC NHXH FE180 PH90 5x cross section A2 Ventilator power supply 3x400V for iSWAY FC WFC RFC NHXCH FE180 PH90 4x cross section C1 Control power supply cable 24 VDC double intake HDGs FE180 PH90 3x1 5 C8 Guaranteed power supply cable TSS X 24 VDC HDGs FE180 PH90 3x2 5 D2 Global FirsBus bus loop HTKSH FE180 PH90 ekw 2x2x0 8 E2 Cables ALARM SAP NC Operation confirmation NO Collective fail...

Страница 75: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 75 Vestibule with transfer Staircase Elevator hall Fire elevator shaft ...

Страница 76: ...ESIGNATION CABLE SORT CABLE TYPE C8 HDGs FE180 PH90 3x2 5 D2 HTKSH FE180 PH90 ekw 2x2x0 8 NOTE Cables for terminals D and D one twist pair CABLE DESCRIPTION DESIGNATION CABLE SORT CABLE TYPE B1 NHXH FE180 PH90 3x1 5 D2 HTKSH FE180 PH90 ekw 2x2x0 8 NOTE Cables for terminals D and D one twist pair CABLE DESCRIPTION DESIGNATION CABLE SORT CABLE TYPE C8 HDGs FE180 PH90 3x2 5 D2 HTKSH FE180 PH90 ekw 2x...

Страница 77: ...B1 NHXH FE180 PH90 3x1 5 D2 HTKSH FE180 PH90 ekw 2x2x0 8 NOTE Cables for terminals D and D one twist pair CABLE DESCRIPTION DESIGNATION CABLE SORT CABLE TYPE C8 HDGs FE180 PH90 3x2 5 D2 HTKSH FE180 PH90 ekw 2x2x0 8 NOTE Cables for terminals D and D one twist pair iSWAY FC WFC RFC device iSWAY FC WFC RFC device iSWAY FC WFC RFC device iSWAY FC WFC RFC device iSWAY FC WFC RFC device iSWAY FC WFC RFC...

Страница 78: ... power supply 230V 16W CABLE DESCRIPTION DESIGNATION CABLE SORT CABLE TYPE B1 NHXH FE180 PH90 3x1 5 D2 HTKSH FE180 PH90 ekw 2x2x0 8 NOTE Cables for terminals D and D one twist pair iSWAY FC WFC RFC device no 1 iSWAY FC WFC RFC device no 4 iSWAY FC WFC RFC device no 2 iSWAY FC WFC RFC device no 3 ...

Страница 79: ...30V 16W CABLE DESCRIPTION DESIGNATION CABLE SORT CABLE TYPE B1 NHXH FE180 PH90 3x1 5 D2 HTKSH FE180 PH90 ekw 2x2x0 8 NOTE Cables for terminals D and D one twist pair iSWAY FC WFC RFC device no 1 iSWAY FC WFC RFC device no 5 iSWAY FC WFC RFC device no 2 iSWAY FC WFC RFC device no 4 iSWAY FC WFC RFC device no 3 ...

Страница 80: ...DESCRIPTION DESIGNATION CABLE SORT CABLE TYPE B1 NHXH FE180 PH90 3x1 5 D2 HTKSH FE180 PH90 ekw 2x2x0 8 NOTE Cables for terminals D and D one twist pair iSWAY FC WFC RFC device no 1 iSWAY FC WFC RFC device no 2 iSWAY FC WFC RFC device no 6 iSWAY FC WFC RFC device no 4 iSWAY FC WFC RFC device no 3 iSWAY FC WFC RFC device no 4 ...

Страница 81: ...ranteed power supply 230V 1kW CABLE DESCRIPTION DESIGNATION CABLE SORT CABLE TYPE B1 NHXH FE180 PH90 3x1 5 D2 HTKSH FE180 PH90 ekw 2x2x0 8 D3 HTKSH FE180 PH90 ekw 2x2x0 8 H1 FTP Cat 5 NOTE Cables for terminals D and D one twist pair iSWAY FC WFC RFC device no 1 iSWAY FC WFC RFC device n iSWAY FC WFC RFC device n m To BMS ...

Страница 82: ...FC RFC device Connection diagram of the double intake to the SzA FCP FCK cabinet iSWAY FC RFC device Connection diagram of the fixed lack of tightness opening damper to the SzA FCP FCK cabinet iSWAY FC WFC RFC device Belimo cable Belimo cable Belimo cable Towards two BELIMO BF24 actuators Damper of the fixed lack of tightness opening BELIMO BF24 Intake auxiliary damper PCR with BLE24 or BEN24 BELI...

Страница 83: ... for terminals D and D one twist pair Connection diagram 24VDC power supply of the TSS X 24V panel to the SzA FCP FCK cabinet iSWAY FC WFC RFC device Connection diagram 24VDC power supply of the peripheral device to the SzA FCP SzA FCK cabinet iSWAY FC WFC RFC device iSWAY FC WFC RFC device iSWAY FC WFC RFC device iSWAY FC WFC RFC device iSWAY FC WFC RFC device Peripheral device mx 60 W Max 4 devi...

Страница 84: ...90 3x1 0 D1 HTKSH FE180 PH90 ekw 2x2x0 8 E1 HTKSH FE180 PH90 1x2x0 8 NOTE Cables for terminals D and D one twist pair iSWAY FC WFC RFC device Optional signal Optional signal Optional signal Optional signal Guaranteed power supply 24V DC 2 2 W Guaranteed power supply 24V DC 2 2 W Guaranteed power supply 24V DC 2 2 W Guaranteed power supply 24V DC 2 2 W ...

Страница 85: ...90 3x1 0 D1 HTKSH FE180 PH90 ekw 2x2x0 8 E1 HTKSH FE180 PH90 1x2x0 8 NOTE Cables for terminals D and D one twist pair iSWAY FC WFC RFC device Guaranteed power supply 24V DC 2 2 W Guaranteed power supply 24V DC 2 2 W Guaranteed power supply 24V DC 2 2 W Guaranteed power supply 24V DC 2 2 W Optional signal Optional signal Optional signal Optional signal ...

Страница 86: ... FE180 PH90 ekw 2x2x0 8 E1 HTKSH FE180 PH90 1x2x0 8 NOTE Cables for terminals D and D one twist pair iSWAY FC WFC RFC device Optional signal Optional signal Optional signal Optional signal Connection diagram for additional P MACF pressure sensors P MACF power supply from MAC FC controller Max 4 devices supplied from an outlet of 24V controller ...

Страница 87: ... FE180 PH90 1x2x0 8 NOTE Cables for terminals D and D one twist pair iSWAY FC WFC RFC device Optional signal Optional signal Optional signal Optional signal Max 4 devices supplied from one outlet of 24V controller Connection diagram for additional P MACF pressure sensor to the SzA FCP FCK cabinet equipped with P MACF pressure sensor P MACF power supply from MAC FC controller ...

Страница 88: ... for terminals D and D one twist pair iSWAY FC WFC RFC device Guaranteed power supply 24V DC 5 W Guaranteed power supply 24V DC 5 W Guaranteed power supply 24V DC 5 W Guaranteed power supply 24V DC 5 W Optional signal Optional signal Optional signal Optional signal Optional signal Power supply unit FAILURE Optional signal Power supply unit FAILURE Optional signal Power supply unit FAILURE Optional...

Страница 89: ... 0 NOTE Cables for terminals D and D one twist pair iSWAY FC WFC RFC device Guaranteed power supply 24V DC 5 W Guaranteed power supply 24V DC 5 W Guaranteed power supply 24V DC 5 W Guaranteed power supply 24V DC 5 W Optional signal Optional signal Optional signal Optional signal Optional signal Power supply unit FAILURE Optional signal Power supply unit FAILURE Optional signal Power supply unit FA...

Страница 90: ...PTION DESIGNATION CABLE SORT CABLE TYPE C4 HDGs FE180 PH90 2x1 5 C7 HDGs FE180 PH90 4x1 5 F2 HTKSH FE180 PH90 3x2x1 0 Guaranteed power supply 24V DC 12 W Guaranteed power supply 24V DC 42 W Control damper with NMQ24A SR BELIMO actuator Control damper with NMQ24A SR BELIMO actuator Control damper with NMQ24A SR BELIMO actuator Control damper with NMQ24A SR BELIMO actuator MAC D Min Finish version 2...

Страница 91: ... FE180 PH90 2x4 C7 HDGs FE180 PH90 4x1 5 F2 HTKSH FE180 PH90 3x2x1 0 Guaranteed power supply 24V DC 36 W Guaranteed power supply 24V DC 48 W Control damper with NMQ24A SR BELIMO actuator Control damper with NMQ24A SR BELIMO actuator Control damper with NMQ24A SR BELIMO actuator Control damper with NMQ24A SR BELIMO actuator Control damper with NMQ24A SR BELIMO actuator Control damper with NMQ24A SR...

Страница 92: ...LE SORT CABLE TYPE C2 HDGsFE180 PH90 3x1 0 D1 HTKSH FE180 PH90 ekw 2x2x0 8 F4 HTKSH FE180 PH90 4x2x1 0 NOTE Cables for terminals D and D one twist pair iSWAY FC WFC RFC device Guaranteed power supply 24V DC Guaranteed power supply 24V DC Guaranteed power supply 24V DC Maximum 8 MAC LINK cards on one LocalFireBUS loop ...

Страница 93: ...ABLE SORT CABLE TYPE C2 HDGsFE180 PH90 3x1 0 D1 HTKSH FE180 PH90 ekw 2x2x0 8 F3 HTKSH FE180 PH90 4x2x1 0 NOTE Cables for terminals D and D one twist pair iSWAY FC WFC RFC device Guaranteed power supply 24V DC Guaranteed power supply 24V DC Guaranteed power supply 24V DC Max 8 MAC LINK cards on one LocalFireBus loop ...

Страница 94: ...Y FC R device iSWAY FC R device iSWAY FC R device is always equipped with an additional P MACF pressure sensor High temperature measurement outside the object Max 4 devices supplied from one output of the 24V controller High temperature measurement inside the object High temperature measurement outside the object High temperature measurement inside the object Max 4 devices supplied from one output...

Страница 95: ... 95 CABLE DESCRIPTION DESIGNATION CABLE SORT CABLE TYPE D1 HTKSH FE180 PH90 ekw 2x2x0 8 NOTE Cables for terminals D and D one twist pair iSWAY FC WFC RFC device iSWAY FC WFC RFC device iSWAY FC WFC RFC device iSWAY FC WFC RFC device equipped with an optional P MACF pressure sensor ...

Страница 96: ...out enclosure there is no service switch 2 1 1 SzA FCK connection For iSWAY FC with enclosure a fan motor a PZS junction box connected to the cut off damper and a smoke detector are connected during production while for iSWAY without enclosure these connections must be made on site GUARANTEED POWER SUPPLY 3X400V FROM THE SUBSTATION CABLES DESCRIPTION DESIGNATION CABLE SORT CABLE TYPE A1 NHXH FE180...

Страница 97: ... inverter PZS connection box Smoke detector Shut off damper SRC D CDH K Ventilator motor CABLES DESCRIPTION DESIGNATION CABLE SORT CABLE TYPE C NHXCH FE180 PH90 4XDIAMETER DEPENDING ON THE CAPACITY F1 HTKSH FE180 PH90 2x2x1 0 G1 HTKSH FE180 PH90 3x2x0 8 Option DESIGNATION CABLE SORT CABLE TYPE E OWY OMY 3x1 5 ...

Страница 98: ...lary iSWAY system without a housing and recommended cable types are presented in the block diagram below Fig 14 5 Double air intake system Key Control and Display Panel Static measurement of pressure difference Ø5 impulse cables Damper BLE24 BELIMO actuator Rescue crews access point monitoring room WIRING Designation on the diagram Automation elements connections Cable type A1 Guaranteed power sup...

Страница 99: ...SWAY FC WFC RFC NHXH FE180 PH90 5x cross section A2 Ventilator power supply 3x400V for iSWAY FC WFC RFC NHXCH FE180 PH90 4x cross section B1 Guaranteed power supply 1x230VAC MSPU TS TSS NHXH FE180 PH90 3x1 5 C1 Control power supply cable 24 VDC double intake HDGs FE180 PH90 3x1 5 D2 Global FirsBus bus loop HTKSH FE180 PH90 ekw 2x2x0 8 E2 Cables ALARM SAP NC Operation confirmation NO Collective fai...

Страница 100: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 100 ...

Страница 101: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 101 ...

Страница 102: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 102 ...

Страница 103: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 103 ...

Страница 104: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 104 ...

Страница 105: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 105 ...

Страница 106: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 106 ...

Страница 107: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 107 ...

Страница 108: ...r Power supply VAC Power consumption kW iSWAY FC 0 3 AFC AJF 560 3x400 2 2 0 12 AFC AJF 560 3x400 4 0 1 17 AFC ARC AJF 800 3x400 4 0 1 20 AFC ARC AJF 800 3x400 5 5 1 24 AFC ARC AJF 800 3x400 7 5 2 31 AFC ARC AJF 1000 3x400 7 5 2 39 AFC ARC AJF 1000 3x400 11 2 47 AFC ARC AJF 1000 3x400 15 2 75 AJF 1000 3x400 18 5 ...

Страница 109: ... WFC 1 1 HCBT 4 560 3x400 1 3 1 5 HCBT 4 630 3x400 1 7 2 2 HCBT 4 710 3x400 2 6 3 0 HCBT 4 800 3x400 3 0 5 5 HCBT 4 900 3x400 5 5 Type of device Type Diameter Power supply VAC Power consumption kW iSWAY RFC 1 5 iSFS 56 T4 3x400 1 5 2 2 iSFS 63 T4 3x400 2 2 3 0 iSFS 80 T4 3x400 3 0 4 0 iSFS 80 T4 3x400 4 0 5 5 iSFS 100 T4 3x400 5 5 7 5 iSFS 100 T4 3x400 7 5 ...

Страница 110: ...DTR iSWAY Set of products Version 2 1 of 3 2022 110 SzA FCP 0 3 0 12 1 17 1 20 1 24 2 31 2 39 2 47 2 75 Inverter power kW 2 2 4 0 4 0 5 5 7 5 7 5 11 0 15 0 18 5 Overcurrent protection of the inverter B10 B16 B16 B16 B20 B20 B32 B40 B50 ...

Страница 111: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 111 ...

Страница 112: ... DTR iSWAY Set of products Version 2 1 of 3 2022 112 SzA FCK 1 1 1 5 2 2 3 0 4 0 5 5 7 5 11 15 18 5 Inverter power kW 1 1 1 5 2 2 3 0 4 0 5 5 7 5 11 15 18 5 Overcurrent protection of the inverter B6 B6 B10 B10 B16 B16 B20 B32 B40 B50 ...

Страница 113: ...t IP66 inverter can be delivered Table 14 7 Series of frequency inverters used in iSWAY WFC Type of device Type Power supply VAC Power kW iSWAY WFC 1 1 VLT FC102 IP20 3x400 1 1 1 5 VLT FC102 IP20 3x400 1 5 2 2 VLT FC102 IP20 3x400 2 2 3 0 VLT FC102 IP20 3x400 3 0 5 5 VLT FC102 IP20 3x400 5 5 On request IP66 inverter can be delivered Table 14 8 Series of frequency inverters used in iSWAY RFC Type o...

Страница 114: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 114 On request IP66 inverter can be delivered ...

Страница 115: ...WD500 130 2 1 24 BWD600 080 2 2 31 BWD600 080 2 2 39 BWD600 080 2 2 47 BWD600 072 2 2 75 175U3339 1 Type of device Resistor type Number of resistors iSWAY WFC 1 1 BWD500 430 1 1 5 BWD500 430 1 2 2 BWD500 310 1 3 0 BWD500 210 1 5 5 BWD500 130 2 Type of device Resistor type Number of resistors iSWAY RFC 1 5 BWD500 430 1 2 2 BWD500 310 1 3 0 BWD500 210 1 4 0 BWD500 300 2 5 5 BWD500 130 2 7 5 BDW600 0...

Страница 116: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 116 Earthing terminals of the device ...

Страница 117: ... 3 2022 117 Line with fault monitoring Line condition monitoring resistors 1 LFB loop break 2 No communication with the inverter 3 GFB loop break 4 Fire action 5 Collective fault 6 Blinking correct operation of the programme Switched on diode means Power supply confirmation ...

Страница 118: ...ion and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 118 24V power supply Local Local Global Global Inverter RS485 Inverter Shut off damper Auxiliary intake Phase sensor Smoke sensor SAP ...

Страница 119: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 119 ...

Страница 120: ...iSWAY FC 0 SzA FCP Step 1 The inspection panel should be removed For this purpose we dismantle the yoke joints 6 in total placed in the vertical plane of the device Step 2 Then dismantle the inspection panel in the bulkhead wall on which the automation devices are hung After removing the inspection sheet the heater is located to the right of the window ...

Страница 121: ...oducts Version 2 1 of 3 2022 121 Step 3 Check and clean the area around the infrared heater The presence of any objects grass sticks rags gloves etc near the radiator is prohibited Step 4 Screw back the inspection panel closing the window 4 screws Step 5 ...

Страница 122: ...nspection panel by securing it with the yoke joints 6 pieces II Instructions for checking the cleanliness of the infrared heater iSWAY FC 1 SzA FCP Step 1 Remove 2 inspection panels For this purpose we dismantle the yoke joints 4 per each panel 8 in total placed in the vertical plane of the device ...

Страница 123: ... inspection panel in the bulkhead wall on which the automation devices are hung After removing the inspection sheet the heater is located to the right of the window Step 3 Check and clean the area around the infrared heater The presence of any objects grass sticks rags gloves etc near the radiator is prohibited ...

Страница 124: ...nd Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 124 Step 4 Screw back the inspection panel closing the window 4 screws Step 5 Attach inspection panel 2 by securing them with the yoke joints 8 ...

Страница 125: ...WAY FC 2 SzA FCP Step 1 Remove 2 inspection panels For this purpose we dismantle the yoke joints 4 per each panel 8 in total placed in the vertical plane of the device Step 2 Then dismantle the inspection panel in the bulkhead wall on which the automation devices are hung After removing the inspection sheet the heater is located to the right of the window ...

Страница 126: ... products Version 2 1 of 3 2022 126 Step 3 Check and clean the area around the infrared heater The presence of any objects grass sticks rags gloves etc near the radiator is prohibited Step 4 Screw back the inspection panel closing the window 4 screws ...

Страница 127: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 127 Step 5 Attach inspection panel 2 by securing them with the yoke joints 8 ...

Страница 128: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 128 ...

Страница 129: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 129 ...

Страница 130: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 130 1 Cover of electrics 2 LED diode red yellow green 3 Zeroing button ...

Страница 131: ...ered as standard On request IP65 class can be delivered For details and technical information see DTR P MAC and P MACF Connection and wiring diagrams can be found in section 13 Name Dimension mm Length 128 Height 51 Width 88 Hole diameter for the gland 28 Number of glands 6 Cable diameter range min max mm 8 0 26 Diaphragm ventilator Part list No Qty Name Diameter range min max mm SWxE key size mm ...

Страница 132: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 132 Terminals of the cooperating device Line with fault monitoring Line monitoring resistors ...

Страница 133: ...nance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 133 1 Cover of electrics 2 SMD diodes signalling device operation parameters Wall bracket 4 pcs Part list No Qty Name Diameter range min max mm SWxE key size mm ...

Страница 134: ...ed 4 Zeroing button 5 USB service socket 6 Pressure stub pipes 7 Earthing assembly 8 Diaphragm ventilator 9 USB transmission signalization 10 Cover of electronics 11 LED diode green power supply confirmation 12 LED diode yellow green red 13 Zeroing button 14 USB service socket 15 Pressure stub pipes 16 Earthing assembly 17 Diaphragm ventilator 18 USB transmission signalization ...

Страница 135: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 135 Designation Name Dimension mm Width Height Length ...

Страница 136: ...DTR iSWAY Set of products Version 2 1 of 3 2022 136 Item No Quantity Name Diameter range min max mm P1 1 UNI Pass 4 0 8 0 P2 1 UNI Pass 3 5 6 0 P3 1 UNI Pass 3 5 6 0 P4 1 UNI Pass 6 0 12 0 P5 1 UNI Pass 5 0 10 0 P6 1 UNI Pass 5 0 10 0 ...

Страница 137: ...et of products Version 2 1 of 3 2022 137 Item No Quantity Name Diameter range min max mm P1 1 UNI Pass 4 0 8 0 P2 1 UNI Pass 3 5 6 0 P3 1 UNI Pass 3 5 6 0 P4 1 UNI Pass 6 0 12 0 P5 1 UNI Pass 5 0 10 0 P6 1 UNI Pass 5 0 10 0 P7 1 UNI Pass 6 0 12 0 ...

Страница 138: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 138 ...

Страница 139: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 139 ...

Страница 140: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 140 ...

Страница 141: ...ation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 141 A mm B mm C mm D mm E mm PZ1 198 203 155 105 80 PZ2 198 203 155 105 80 PZ3 248 253 205 155 100 PZ4 308 283 265 4 185 4 129 5 ...

Страница 142: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 142 ...

Страница 143: ...4 VDC 20 20 Digital inputs option I applies to all inputs with line fault monitoring Designed to work with dry contacts Uout Usupply max 28 8 VDC Iout 2 mA Analogue inputs option IA 0 10 VDC Digital outputs option O Dry contacts 30 VDC max 2 A Analogue outputs option OA 0 10 VDC 4 20 mA Protection class IP54 or optionally IP65 ...

Страница 144: ...and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 144 Designation Name Dimension mm Width Height Length Hole diameter for a gland Note The given dimensions are inner dimensions of the housing ...

Страница 145: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 145 ...

Страница 146: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 146 Mounting dimensions Overall dimensions SxW mm SxWxG mm 160x320 210x340x188 ...

Страница 147: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 147 Mounting dimensions Overall dimensions SxW mm SxWxG mm 260x320 305x340x188 ...

Страница 148: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 148 Mounting dimensions Overall dimensions SxW mm SxWxG mm 260x320 305x340x188 ...

Страница 149: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 149 Mounting dimensions Overall dimensions SxW mm SxWxG mm 260x620 313x640x188 ...

Страница 150: ...g of the ventilator 4 a yellow light signal informing about the smoke in the unit 5 2 position switch controlling the lock of the smoke sensor or double intake switch 6 Diaphragm ventilator 7 EMC cable gland 8 a red light signal indicating a SAP fire 9 a green light signal indicating power supply to the panel 10 2 position switch controlling cancelation of SAP fire 11 UNI cable gland 12 Wall mount...

Страница 151: ...g of the ventilator 4 a yellow light signal informing about the smoke in the unit 5 2 position switch controlling the lock of the smoke sensor or double intake switch 6 Diaphragm ventilator 7 EMC cable gland 8 a red light signal indicating a SAP fire 9 a green light signal indicating power supply to the panel 10 2 position switch controlling cancelation of SAP fire 11 UNI cable gland 12 Wall mount...

Страница 152: ...g of the ventilator 4 a yellow light signal informing about the smoke in the unit 5 2 position switch controlling the lock of the smoke sensor or double intake switch 6 Diaphragm ventilator 7 EMC cable gland 8 a red light signal indicating a SAP fire 9 a green light signal indicating power supply to the panel 10 2 position switch controlling cancelation of SAP fire 11 UNI cable gland 12 Wall mount...

Страница 153: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 153 ...

Страница 154: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 154 ...

Страница 155: ...l DTR iSWAY Set of products Version 2 1 of 3 2022 155 No TS Dimensions Installation Overall SxW mm SxWxG mm TS 4 TS 6 260x320 313x340x188 TS 7 TS 16 556x449 605x522x263 TS 17 TS 32 556x649 605x722x263 TS 33 TS 36 756x849 805x922x313 ...

Страница 156: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 156 ...

Страница 157: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 157 ...

Страница 158: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 158 ...

Страница 159: ... Screen size 23 8 16 9 Resolution 1920x1080 Supply voltage 12 VDC Power consumption 18 W Protection class from the front IP66 Touch technology Capacitive PCT Number of touch points 10 Installation Wall or desk bracket VESA 75 standard 230 VAC 12 VDC power supply included with the MSPU ...

Страница 160: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 160 ...

Страница 161: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 161 ...

Страница 162: ...status of the controller with 401 address 05 regulator pressure of the 402 address 06 relative address and status of the controller with 402 address 07 regulator pressure of the 403 address 08 relative address and status of the controller with 403 address 09 regulator pressure of the 404 address 10 relative address and status of the controller with 404 address 65 regulator pressure of the 432 addr...

Страница 163: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 163 o ...

Страница 164: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 164 Rys 15 37 ...

Страница 165: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 165 ...

Страница 166: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 166 ...

Страница 167: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 167 ...

Страница 168: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 168 ...

Страница 169: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 169 ...

Страница 170: ...control systems Part 6 Specification for differential pressure systems Kits of Equipment 12 Acceptance tests 12 1 General provisions The design recommendations given in this document assume that pressure differential systems are designed to overcome both the pressures of the chimney effect caused by non pressurised ...

Страница 171: ...fans to operate for at least 10 minutes to stabilize air temperatures b Switch off the fans of the differential pressure system leaving all other components in their operating mode c Measure the pressure difference between the pressurised space and the corresponding utility room d Measure the difference between the staircase where the pressure will be increased and a suitable utility room on at le...

Страница 172: ...tely the air velocity take at least 8 measurements evenly distributed throughout the doorway Calculate the arithmetic mean of these measurements or alternatively move the corresponding measuring device evenly across the open door and record the average air speed 12 2 3 5 The calibration of all test equipment shall be such that the measurements are accurate to 5 12 2 4 Door opening force 12 2 4 1 T...

Страница 173: ...s should be kept by the building management Any records should show repeated faults so that potential system defects can easily be traced 13 2ndMaintenance requirements 13 2 1 The equipment should be included in the maintenance schedule of the building services 13 2 2 A maintenance and functional test schedule must be prepared 13 2 3 All unsatisfactory results or faults in the maintenance of the e...

Страница 174: ...rocedures in 12 2 1 12 2 2 12 2 3 and 12 2 4 in sequence 13 6th Repeated tests The entire differential pressure system shall be re tested in accordance with 12 1 acceptance tests following any modification of the building which may have affected the differential pressure system e g changes in internal divisions extension and changes in the differential pressure system 13 7th Test results The resul...

Страница 175: ...3 2022 175 c Inspection hatches shall be provided in ducts in the vicinity of control dampers and fire dampers d There shall be sufficient free space around the generators e To ensure safe access to manual triggering mechanisms of the flaps if any access panels must be placed ...

Страница 176: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 176 ...

Страница 177: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 177 ...

Страница 178: ...from the date of detection of a defect making the product available in the condition in which the defect appeared together with a detailed description of the technical problem and documents confirming the performance of all inspections periodic checks and maintenance if applicable provided by the Warrantor and the applicable regulations Complaints are filed by sending the completed form Applicatio...

Страница 179: ...f repair and shall lose the warranty granted to it 15 The warranty is valid if a the products system components which have been sealed at the factory if applicable are intact and original or have been fitted by the Warrantor or a seal service authorized by the Warrantor b the products system elements are fully identifiable in particular they have intact legible rating plates if any c all periodica...

Страница 180: ... of the Terms and conditions of storage and transport of lacquer products instructions manual available at www smay pl when repairs and interferences in the system were made by unauthorized persons and not authorized by the Warrantor 18 The warranty does not cover damage caused directly or indirectly by force majeure events such as in particular flood fire lightning etc 19 In the event of unjustif...

Страница 181: ...Operation and Maintenance Manual DTR iSWAY Set of products Version 2 1 of 3 2022 181 ...

Отзывы: