HMU8-860 ATS Remote Monitoring Controller User Manual Page 24 of 50
6
SCOPES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS
6.1
PARAMETER CONTENTS AND SCOPES OF MONITORING MODULE
Table 16 – Parameter Contents and Scopes
No.
Item
Range
Default
Description
RS485-1 Setting
1
Module Address
(1-254)
001
The module address of current RS485
interface communicates with the master
control module.
2
Baud Rate
(0-3)
2
0: 2400bps
1: 4800bps
2: 9600bps
3: 19200bps
3
Parity Bit
(0-2)
0
0: None
1: Odd Parity
2: Even Parity
4
Stop Bit
(1-2)
2
1: 1 Bit
2: 2 Bits
RS485-2 Setting (Reserved)
1
Module Address
(1-254)
001
The module address of current RS485
interface is not used when communicating
with the master control module.
2
Baud Rate
(0-3)
2
0: 2400bps
1: 4800bps
2: 9600bps
3: 19200bps
3
Parity Bit
(0-2)
0
0: None
1: Odd Parity
2: Even Parity
4
Stop Bit
(1-2)
2
1: 1 Bit
2: 2 Bits
RS485-3 Setting (Reserved)
1
RS485-3 Module
Address
(1-254)
001
The module address of current RS485
interface is not used when communicating
with the master control module.
2
RS485-3
Baud
Rate
(0-3)
2
0: 2400bps
1: 4800bps
2: 9600bps
3: 19200bps
3
RS485-3 Parity Bit
(0-2)
0
0: None
1: Odd Parity
2: Even Parity
4
RS485-3 Stop Bit
(1-2)
2
1: 1 Bit
2: 2 Bits