![Smartgen HGMS62 Скачать руководство пользователя страница 24](http://html1.mh-extra.com/html/smartgen/hgms62/hgms62_user-manual_1297538024.webp)
HGMS62 Split Type Genset Controller User Manual Page 24 of 58
Table 11 – HGMS62D Terminal Connection Description
No.
Function
Cable Size
Description
1
RX232
TXD
0.5mm
2
Connect master controller HGMS62M.
Shielding line is required, shielded layer is connected
to terminal 4 GND.
2
RXD
0.5mm
2
3
NC
4
GND
1.5mm
2
Connect negative of controller power.
5
B-
1.5mm
2
6
B+
1.5mm
2
Connect positive of controller power.
7.3
HGMS62 WIRE HARNESS DESCRIPTION
Table 12 – HGMS62 Wire Harness Description
Harness Port
Harness Length
Diagram
No.
Function
Cable Size
XS-HGMS62DM
XS-HGMS62DM-S
1
MAINS N
1.0mm
2
0.55m
1.05m
2
MAINS R
1.0mm
2
3
1.5mm
2
4
CHARGE-
1.5mm
2
2
B+ OUT1
1.5mm
2
0.65m
0.6m
3
B-
1.5mm
2
4
RS232 RXD
0.5mm
2
5
RS232 TXD
0.5mm
2
7
GND
0.5mm
2
1
B+ IN
1.5mm
2
0.85m
0.85m
6
B+ OUT
1.5mm
2
8
EM.STOP OUT
1.5mm
2
0.75m
1.5m
9
EM.STOP IN
1.5mm
2
1
FUEL
1.5mm
2
0.4m
1.0m
2
MP1
0.5mm
2
3
GND
1.5mm
2
4
MP2(GND)
0.5mm
2
7
ACTUATOR
SIGNAL 2
1.5mm
2
10
ACTUATOR
SIGNAL 1
1.5mm
2
9
AUX.
OUTPUT 2
1.5mm
2
12
5
NC
/
/
6
NC
/
/
8
NC
/
/
11
NC
/
/