HGMS62 Split Type Genset Controller User Manual Page 19 of 58
6.4
TRIP ALARMS
When controller detects trip alarm signal, it will disconnect close signal immediately while genset
will not stop.
Table 9 – Trip Alarms
No.
Trip
Description
1 Over Current
When genset current is higher than threshold and overcurrent action
selects “Trip”, controller will send trip alarm signal.
2 Reverse Power
When genset reverse power value (power is negative) is higher than
threshold, and reverse power action selects “Trip”, controller will send
trip alarm signal.
3 Over Power
When genset power value (power is positive) is higher than threshold,
and over power action selects “Trip”, controller will send trip alarm
signal.
4 Input Trip
When input port is configured as “Trip” and active, controller will send
trip alarm signal.