HGM8151 Genset Parallel Controller User Manual Page 53 of 66
WARNING!
When there is load c
urrent, transformer’s secon
dary side prohibit open circuit.
14.6
WITHSTAND VOLTAGE TEST
CAUTION!
When controller had been installed in control panel, if need the high voltage test, please disconnect
controller’s all terminal connections, in order to prevent
high voltage into controller and damage it.
15
GSM SHORT MESSAGE ALARM AND REMOTE CONTROL
15.1
GSM SHORT MESSAGE ALARM
When controller detects alarm, it will send short message to phone automatically.
NOTE:
All alarms about shutdown, trip and stop and trip will be sent to the pre-set phone. Warnings are sent to the
phone according to the pre-set.
15.2
GSM SHORT MESSAGE REMOTE CONTROL
Users send order message to GSM module, then controller will make actions according to this SMS
order and pass back corresponding operations information. Controllers only execute the orders by
pre-set.
Table 18 SMS Orders List
No.
SMS Orders
Pass back Information
Description
1
SMS GENSET
GENSET ALARM
When genset is stopping
alarm
Get status
of genset
SYSTEM IN STOP MODE
GENSET AT REST
At rest status in stop mode
SYSTEM IN MANUAL MODE
GENSET AT REST
At rest status in manual
mode
SYSTEM IN AUTO MODE
GENSET AT REST
At rest status in Auto mode
SYSTEM IN STOP MODE
GENSET IS RUNNING
Running status in stop
mode
SYSTEM IN MANUAL MODE
GENSET IS RUNNING
Running status in manual
mode
SYSTEM IN AUTO MODE
GENSET AT RUNNING
Running status in stop
mode
2
SMS START
GENSET ALARM
Generator
is
shutdown
alarm or trip alarm
Start
genset
STOP MODE NOT START
Cannot start in stop mode
SMS START OK
Start in manual mode
AUTO MODE NOT START
Cannot start in auto mode
3
SMS STOP MODE
SMS STOP OK
Set as stop mode
4
SMS MANUAL MODE
SMS MANUAL MODE OK
Set as manual mode
5
SMS AUTO MODE
SMS AUTO MODE OK
Set as auto mode