HGM8110DC-2 GENSET CONTROLLER USER MANUAL
HGM8110DC-2 Genset Controller 2020-02-20 Version 1.0 Page 30 of 69
8
SCOPES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS
8.1
CONTENTS AND SCOPES OF PARAMETERS
Table 13 - Parameters Contents and Scopes
No.
Items
Parameters
Defaults
Description
DC Generator
1
Work Mode
(0~2)
0
0: DC;
1: AC;
2: DC+AC;
2
Rated Voltage
(10~30000)V
500
Standard for checking DC generator
over/under voltage.
3
Loading Voltage
(0-100)%
90
Setting value is DC generator rated
voltage‘s percentage. The controller
detects in the preparation of the load
period, and does not enter the normal
running period when the generator voltage
is less than the load voltage.
4
PT Ratio
(10-30000)V/10V
1000
Ratio of the external connected DC voltage
transformer.
5
Rated Current
(10-6000)A
300
Rated full load current of DC generator,
which is used as the standard for load
power.
6
CT Ratio
(10-6000)A/20mA 400
Ratio of the external connected DC current
transformer.
7
Rated Power
(10-6000)kW
100
It is rated power for DC generator, which is
used as the standard for load power.
8
Over Voltage
Shutdown
0: Disable
1: Enable
1
Alarm is detected after enabled; not
detected if it is disabled.
(0-200)%
120
Set value is DC generator
rated voltage‘s
percentage, alarm starts if it is above the
set value.
(0-3600)s
1
Alarm starts when voltage gets up to the
alarm value and this delay is expired.
9
Under Voltage
Shutdown
0: Disable
1: Enable
1
Alarm is detected after enabled; not
detected if it is disabled.
(0-200)%
80
Set value is DC generator rated voltag
e‘s
percentage, alarm starts if it is below the
set value.
(0-3600)s
1
Alarm starts when voltage gets up to the
alarm value and this delay is expired.
10
Over Voltage
Warn
0: Disable
1: Enable
1
Alarm is detected after enabled; not
detected if it is disabled.
(0-200)%
110
Set value is DC generator
rated voltage‘s
percentage, alarm starts if it is above the