HGM8110DC-2 GENSET CONTROLLER USER MANUAL
HGM8110DC-2 Genset Controller 2020-02-20 Version 1.0 Page 27 of 69
7
WIRINGS CONNECTION
HGM8110DC-2
controller‘s back panel is as below:
Fig.2 - Controller Back Panel
Table 12 - Terminal Wiring Connection
No.
Function
Cable Size
Remarks
1
B-
2.5mm
2
Connected with negative of starter battery
2
B+
2.5mm
2
Connected with positive of starter battery. If wire length
is over 30m, better to double wires in parallel. Max. 20A
fuse is recommended.
3
Emergency stop
2.5mm
2
Connected with B+ via emergency stop button
4
Fuel relay output
1.5mm
2
B+ is supplied by No.3 terminal, rated 16A
5
Start relay output
1.5mm
2
B+ is supplied by No.3 terminal,
rated 16A
Connected to
starter coil
6
Aux. Output 1
1.5mm
2
B+ is supplied by No.2 terminal,
rated 7A
Details see Table
14
7
Aux. Output 2
1.5mm
2
B+ is supplied by No.2 terminal,
rated 7A
8
Aux. Output 3
1.5mm
2
B+ is supplied by No.2 terminal,
rated 7A