HGM8110A/8120A Genset Controller User Manual Page 14 of 57
Table 6 Power Factor
NOTE:
1.
Input active power, generator or mains supplies electricity to load;
2.
Output active power, load supplies electricity to generator or mains;
3.
Input reactive power, generator or mains sends reactive power to load;
4.
Output reactive power, load sends reactive power to generator or mains.
★
Engine
, including as below,
Speed, engine temperature, engine oil pressure, liquid (fuel) level, flexible sensor 1, flexible sensor 2,
battery voltage, charger voltage, accumulated run time, accumulated start times.
★
Alarm:
Display all kinds of alarm information, such as Gen Overvoltage, Gen Undervoltage, Gen Over Frequency,
Gen Under Frequency and so on.
★
Event log
Records all start/stop events (shutdown alarm, trip and stop alarm, manual/auto start or stop) and the
real time when alarm occurs.
Example:
4.3.2
BASIC PARAMETER SETTING MENU
Basic parameters setting including as following,
★
Mains Rated Voltage (HGM8120A)
★
Mains Rated Frequency (HGM8120A)
★
Crank Disconnect Condition
★
Flywheel Teeth
Power Factor
Conditions
Active Power Reactive Power
Remark
COS>0L
P>0, Q>0
Input
Input
Load is inductive resistance.
COS>0C
P>0, Q<0
Input
Output
Load is capacitance resistance.
COS<0L
P<0, Q>0
Output
Input
Load equal to one under
excitation generator
COS<0C
P<0, Q<0
Output
Output
Load equal to one over excitation
generator.
Gen
UL-L 0 0 0V
UL-N
0 0 0V
F = 0.0Hz 0rpm
Stop Mode
Load
Current 0.0 0.0 0.0A
Power
0.0kW 0.0 kVA
cosΦ = 0.00 0.0 kVar
Gen Overvoltage Warn