HGM6100N-RM REMOTE MONITORING MODULE USER MANUAL
HGM6100N-RM Remote Monitoring Module 2019-08-06 Version 1.0 Page 13 of 14
7 INSTALLATION
7.1 FIXING CLIPS
—
Controller design is panel installation method, and it is fixed by clips.
—
Withdraw the fixing clip screw (turn anticlockwise) until it reaches proper position.
—
Pull the fixing clip backwards (towards the back of the module) ensuring four clips are inside
their allotted slots.
—
Turn the fixing clip screws clockwise until they are fixed on controller panel.
—
Care should be taken not to over tighten the screws of fixing clips.
7.2 OVERALL DIMENSION AND PANEL CUTOUT
Fig. 5 Case Dimensions and Cutout
HGM6100N-RM controller can be applicable for (8~35) V DC battery voltage environment. Battery
negative must be reliably connected to engine shell. The connection wire between controller power
and battery negative and positive should not be less than 2.5mm
2
. If a float charger is fitted, please
connect output line of the charger with battery negative and positive directly, and then connect
battery positive and negative to power input of controller separately, for the purpose of preventing
charger disturbing the normal running of controller.