HGM501Genset Controller 

HGM501 Genset Controller              Version V1.0              2012-07-10                  Page 7 of 15 
 

2.  During  normal  operation  the button  switches  to 

the lower LED.   

4.2. START/STOP OPERATION 

4.2.1 

STARTING PROCEDURE 

In  stop  mode  turn  the  starter  key  from  OFF  to  ON  position  to  power  on  the 

controller, then change the starter key position to START to begin cranking; after 
the  engine  fires,  release  the  starter  key,  and  voltage,  power  and  frequency 

windows  will  show  the  real  measured  values.  Press 

  or 

  button  to 

switchover  between  indicators  1#-6#  and  multifunctional  window  will  show 

corresponding settings. Press 

  button to return to the frequency window. 

LED indicators state:   

1#      Frequency (Hz)                   
2#      Current (A)                         

 

3#      Battery voltage (V)           

 

4#      Run time (H)                   

 

 

5#      Engine temp.(

)           

 

 

6#      Generator temp.(

)     

 

 

7#      Auto protection               

 If on, auto protection is enabled; if not, it is 
disabled. 

8#      Run on indicator   

              Fuel relay output indicator 

9#      Crank indicator 

 

 

 

Start output indicator 

10#    Engine oil warning 

 

 

Low oil pressure indicator 

NOTE:  Before  starting  the  engine  please  make  sure  that  all  the  parameter 

settings are correct. 

  NOTE

Engine oil warning

indicator operates according to the oil pressure 

switch. Before the start of the gen-set, the light must be on; if it is not, it means that 
oil pressure switch or its return circuit is faulty; in this case please do not proceed 
before clearing up the problem. 

4.2.2 STOPPING PROCEDURE 

Auto stop 

If  auto  protection  condition  occurs,  the  system  will  be  stopped 

automatically; 

During normal running of the gen-set, if low oil pressure signal is detected, 

the set will be stopped. 

Manual stop 

Under any circumstances, if starter key is turned from ON to OFF position, 

it will lead to shutdown. 

Содержание HGM501

Страница 1: ...HGM501 Gen set Controller USER MANUAL Smartgen Technology...

Страница 2: ...ronic means or other without the written permission of the copyright holder Smartgen Technology reserves the right to change the contents of this document without prior notice Version History Date Ver...

Страница 3: ...NICAL DATA 5 4 OPERATION 6 4 1 BUTTON DESCRIPTION 6 4 2 START STOP OPERATION 7 4 2 1 STARTING PROCEDURE 7 4 2 2 STOPPING PROCEDURE 7 5 AUTO PROTECTION 8 6 TERMINAL 9 7 CONFIGURABLE PARAMETERS 10 7 1 C...

Страница 4: ...RISTICS 1 Two specialized LED displays single phase voltage display and total active power voltage display calculated using single phase power taking load as balanced 2 Multifunction LED display that...

Страница 5: ...ase 4 wire L and N only AC 30V 360V ph N AC 30V 360V ph N AC 30V 360V ph N Alternator frequency 50 60Hz Start relay output 7A DC12V power supply output Fuel relay output 7A DC12V power supply output C...

Страница 6: ...alarm UP SCROLL 1 During parameter configuration pressing this button increases the set value 2 During normal operation press this button to switch to the upper LED DOWN SCROLL 1 During parameter conf...

Страница 7: ...6 Generator temp 7 Auto protection If on auto protection is enabled if not it is disabled 8 Run on indicator Fuel relay output indicator 9 Crank indicator Start output indicator 10 Engine oil warning...

Страница 8: ...g If the set value is exceeded by 5 7 5 and continuous for more than 3 hours then alarm shutdown will be initiated If the set value is exceeded by 7 5 10 and continues for more than 1 hours alarm shut...

Страница 9: ...after Safety On Delay when voltage frequency overload high temperature protection is initiated fuel output deactivates 6 TERMINAL HGM501 controller back panel is shown below Terminal connections desc...

Страница 10: ...lock START input 1 5mm2 Hand turn start start relay output Output activates when electric lock key is turned to START position 11 Start relay output 1 5mm2 Rated current 7A power supplied by terminal...

Страница 11: ...4 Select this according to the used sensor 7 2 PARAMETER CONFIGURATION Before using controller for the first time parameters must be configured rated voltage rated frequency rated power set values mus...

Страница 12: ...nd auto protection will continue to be enabled use or to make indicator off and press to disable auto protection When the light indicator is off it means that auto protection is disabled Enabling this...

Страница 13: ...sure all parameters are configured correctly and oil pressure light is on 3 Ensure the controller DC power supply is fused and correctly connected to the positive and negative of starter battery 4 Tak...

Страница 14: ...oller is designed for panel mounting it is held with the help of fixing clips Overall and cutout dimensions can be seen below unit mm 1 Battery Voltage Input NOTE HGM501 controller is suitable for 9 1...

Страница 15: ...n generator is on load C T secondary must not be open circuit 2 Withstanding voltage test CAUTION If withstanding voltage test is conducted after the controller has already been installed onto the con...

Отзывы: