sensor input
7
Low oil pressure input
Low oil pressure digital
or sensor signal input
port;
must
be
connected to B-
8
Battery negative input B-
1.5
mm
2
Controller power supply
input B-
9
Electric lock ON signal
input B+
1.5
mm
2
Controller power supply
input B+ and fuel relay
output (activates when
Electric key is turned to
ON position)
10
Electric lock START input 1.5
mm
2
Hand-turn start, start
relay output (Output
activates when electric
lock key is turned to
START position)
11
Start relay output
1.5
mm
2
Rated
current
7A;
power
supplied
by
terminal 13
12
Fuel relay output
1.5
mm
2
Rated
current
7A;
power
supplied
by
terminal 13
13
Fuel/start relay common
port
2.5
mm
2
Fused and connected
to start battery positive
7. CONFIGURABLE PARAMETERS
7.1.
CONFIGURABLE PARAMETERS TABLE
No
Parameter
Range
Default
factory
value
Description
1
AC system
1P
2P
3P
1P
1P
:
1P2W
2P
:
2P3W
3P
:
3P4W
2
Rated
voltage
110 V
115 V
120 V
130 V
220 V
230 V
240V
220
Generator rated voltage
value selection