HAT833 Series Three Power ATS Controller User Manual Page 41 of 56
9.3.3
CUSTOM COMBINED
Defined combination output is composed by 3 parts, OR condition output SW1, OR condition
output SW2, AND condition output SW3.
SW1 or SW2 is
TRUE
, while SW3 is
TRUE
, Defined combination output is active;
SW1 and SW2 are
FALSE
, or SW3 is
FALSE
, Defined combination output isdeactivated.
NOTE 4:
SW1, SW2, SW3 can be set as any contents except for “defined combination output” in the output setting.
NOTE 5:
3 parts of defined combination output (SW1, SW2, SW3) couldn’t include or recursively include
themselves.
Example,
Contents of OR condition output SW1: input port 1 is active;
Close when OR condition output SW1 is active /inactive: close when active (disconnect when
inactive);
Contents of OR condition output SW2, input port 2 is active;
Close when OR condition output SW2 is active /inactive: close when active (disconnect when
inactive);
Contents of AND condition output SW3: input port 3 is active;
Close when AND condition output SW3 is active /inactive: close when active (disconnect when
inactive);
When input port 1 active or input port 2 active, if input port 3 is active, Defined combination output is
outputting; If input port 3 inactive, Defined combination output is not outputting;
When input port 1 inactive and input port 2 inactive, whatever input port 3 is active or not, Defined
combination output is not outputting.