HAT828 High Speed ATS Controller User Manual Page 18 of 56
7
START/STOP OPERATION
7.1
MANUAL START/STOP
7.1.1
PANEL START/STOP
In the main screen, select “6. Genset Start/Stop” interface when system type is “S1 Mains S2 Gen,
S1 Gen S2 Mains, S1 Mains S2 Mains”, then enter manual start operation interface.
Return
Genset Stop
Genset Start
Press “Up/Down” key to choose parameters (the current line was
highlighted with black) and then press “Confirm” key to confirm.
Genset Stop:
Disconnect the start signal, i.e. stop the running genset.
Genset Start:
Output the start signal, i.e. start the genset.
When system type is “S1 Gen S2 Gen”, manual start/stop menu interface is as follows:
Return
S1 Genset Stop
S1 Genset Start
S2 Genset Stop
S2 Genset Start
Press “Up/Down” key to choose parameters (the current line was
highlighted with black) and then press “Confirm” key to confirm.
S1 Genset Stop:
Disconnect the S1 start signal, i.e. stop the running S1 genset.
S1 Genset Start:
Output the S1 start signal, i.e. start the S1 genset.
S2 Genset Stop:
Disconnect the S2 start signal, i.e. stop the running S2 genset.
S2 Genset Start:
Output the S2 start signal, i.e. start the S2 genset.
7.1.2
REMOTE COMMUNICATION START/STOP
Send remote start/stop signals using MODBUS protocol via RS485 port.
Remote Communication Stop:
Disconnect the start signal, i.e. stop the running genset.
Remote Communication Start:
Output the start signal, i.e. start the genset.