HAT600P Series ATS Controller User Manual Page 16 of 58
7.2
STATUS DESCRIPTION
Table 9 S1 Power Status
No.
Status Name
Description
1
S1 Normal Identify
S1 normal identification delay
2
S1 Abnormal Identify
S1 abnormal identification delay
3
S1 Voltage Normal
Power value is within the specified range.
4
S1 Voltage None
Voltage is 0.
5
S1 Voltage High
Voltage is above the pre-set upper value.
6
S1 Voltage Low
Voltage is below the pre-set lower value.
7
S1 Frequency High
Frequency is above the pre-set upper value.
8
S1 Frequency Low
Frequency is below the pre-set lower value.
9
S1 Loss of Phase
Loss of one or two phase among A, B, C.
10
S1 Reverse Phase Sequence
Wrong phase sequence A-B-C.
Table 10 S2 Power Status
No.
Status Name
Description
1
S2 Normal Identify
S2 normal identification delay
2
S2 Abnormal Identify
S2 abnormal identification delay
3
S2 Voltage Normal
Power value is within the specified range.
4
S2 Voltage None
Voltage is 0.
5
S2 Voltage High
Voltage is above the pre-set upper value.
6
S2 Voltage Low
Voltage is below the pre-set lower value.
7
S2 Frequency High
Frequency is above the pre-set upper value.
8
S2 Frequency Low
Frequency is below the pre-set lower value.
9
S2 Loss of Phase
Loss of one or two phase among A, B, C.
10
S2 Reverse Phase Sequence
Wrong phase sequence A-B-C.
Table 11 Genset Status
No.
Status Name
Description
1
Start Delay
Delay time before genset start.
2
Stop Delay
Delay time before genset stop.
3
Scheduled Not Start
Display Scheduled Not Start lasting time when it is active.
4
Scheduled Start
Display Scheduled Start lasting time when it is active.
5
S1 Cycle Start
S1 Cycle Start finishing countdown when it is active.
6
S2 Cycle Start
S2 Cycle Start finishing countdown when it is active.
7
S1 Genset Start
Only active when system is "S1 Gen S2 Gen".
8
S2 Genset Start
Only active when system is "S1 Gen S2 Gen".
9
Genset Start
Genset start signal outputs.
10
Genset Standby
None genset signal outputs.