HAT553V ATS Controller User Manual Page 15 of 32
8.2
PARAMETER CONFIGURATION TABLE
Table 16 Parameter Configuration Items
No.
Item
Range
Default
Description
AC Setting
1 A Available Delay
(0-3600)s
10
The check time from A power abnormal to
normal.
2 A Unavailable Delay
(0-3600)s
5
The check time from A power normal to
abnormal.
3 B Available Delay
(0-3600)s
10
The check time from B power abnormal to
normal.
4 B Unavailable Delay
(0-3600)s
5
The check time from B power normal to
abnormal.
5 Set Master
(0-1)
0
0: A Master
1: B Master
6 System Type Set
(0-2)
0
0: A Mains B Gen
1: A Gen B Mains
2: A Mains B Mains
7 AC System
(0-3)
0
0: 3-Phase, 4-Wire
1: 3-Phase, 3-Wire
2: 2-Phase, 3-Wire
3: Single Phase, 2-Wire
Special custom is needed for 3 phase 3 wire
8 Rated Voltage
(0~30000)V
220
Rated voltage value for AC system.
9 Over Volt Set
(0~1)
1
0: Disable 1: Enable
10 Over Volt Value
(0~200)%
120
Voltage upper limit; abnormal when it is over
upper limit.
11 Over Volt Return
(0~200)%
115
Voltage upper limit return value; normal when
it is lower than return value.
12 Under Volt Set
(0~1)
1
0: Disable 1: Enable
13 Under Volt Value
(0~200)%
80
Voltage lower limit; abnormal when it is lower
than this limit.
14 Under Volt Return
(0~200)%
85
Lower limit return value; normal when it is
above return value.
15 Rated Frequency
(10.0~75.0)Hz
50.0
Rated frequency value for AC system
16 Over Freq. Set
(0~1)
1
0: Disable 1: Enable
17 Over Freq. Value
(0~200)%
110
Frequency upper limit; abnormal when it is
above upper limit.
18 Over Freq. Return
(0~ 200)%
104
Upper limit return value; normal when it is
lower than return value.
19 Under Freq. Set
(0~1)
1
0: Disable 1: Enable
20 Under Freq. Value
(0~ 200)%
90
Frequency lower limit value; abnormal when it
is lower than this limit.