10 EVENT LOG
In the first page of the main interface, press
key, and enter menu page. Select "Event Log", and
then select
to confirm. In this way Event Log interface is entered.
Each item of Event Log contents includes:
Date and time at recording;
Type of record;
Event of record;
A power status;
B power status;
A power 3-phase voltage;
B power 3-phase voltage;
A power frequency;
B power frequency;
Event log can be recorded up to max. 50 items. The first one is the newest. Users can check each item
via Down key. When recorded items are over 50, new item will cover the newest record.
Record type includes: Action Event, Warn Event, Fault Event. Fault events are all fault alarms, warn
events are all warning alarms.
Table 20 Action Events
No.
Action Event
Description
1
Closing A
Record when A power close is outputted;
2
Closing B
Record when B power close is outputted;
3
Opening A
Record when A power open is outputted; (HAT553)
4
Opening B
Record when B power open is outputted; (HAT553)
5
Simult. Dual Close
Record when A power and B power takes load simultaneously;
6
Genset Start
Record when genset start signal is outputted;
7
Genset Stop
Record when genset start signal is disconnected;
8
Auto Mode
Record when it is transferred to Auto mode;
9
Manual Mode
Record when it is transferred to Manual mode;