5
PARAMETER SETTING OF PANEL OPERATION
5.1
PANEL OPERATION SETTING
Pressing and holding the
button for more than 3s, all LEDs are illuminated to enter into lamp test
mode; Pressing and holding the
button for more than 7s, all LEDs are flashing (500ms per time) to
enter into parameter setting status, and release
button; If you are not trying to set parameters,
press
button and all LEDs flash quickly for 5 times (once per 200ms) and return to normal test
mode. At lamp test state, release
button, and controller will return to normal test mode. After
entering parameter setting mode, if parameters are not set, controller will automatically return back to
normal test mode after about 1 minute and 30 seconds.
5.2
MASTER SETTING
Firstly, make controller enter parameter setting status and then conduct the setting.
Procedures of setting “S1 Master”, “S2 Master” and “Each Backup”
:
a)
Press
,
and
at the same time, when S1/S2 power indicator and Auto indicator are
illuminated; release the three buttons, then the auto indicator and S2 power indicators extinguish,
S1power indicator illuminates, which means controller master status can be set.
b)
Pressing
can circularly set 3 conditions of power supply:
S1 Master:
S1 power indicator illuminates and S2 power indicator extinguishes
;
S2 Master:
S2 power indicator illuminates and S1 power indicator extinguishes
;
Each Backup:
S1 power and S2 power indicators are illuminated at the same time.
c)
After adjusting, press
, when S1 power indicator, Auto indicator and S2 power indicator are
illuminated, the adjusted power master has been saved. The controller will go back to normal status
automatically after all LEDs are flashing 5 times rapidly and controller will work as the master status.
Once the controller is power on, its master status can be judged by the following three conditions.
—
If S1 power supply indicator flashes rapidly for three times, indicating S1 power supply for master.
—
If S2 power supply indicator flashes rapidly for three times, indicating S2 power supply for master.
—
If S1 and S2 power supply indicators flash simultaneously for three times, indicating it is Each
Backup.