SPECIFICATION
Table 2 – Product Specification
Items
Contents
Operating Voltage
AC supply L1N1/L2N2, voltage range AC (170~277)V.
Power Consumption
<3W (Standby mode: <1W)
AC Voltage Input
3P4W
1P2W
2P3W
3P3W
AC170V~AC277V(ph-N)
AC170V~AC277V (ph-N)
AC170V~AC277V(ph-N)
AC170V~AC277V(ph-ph) (Refer to 3P3W wiring diagram)
Rated Frequency
50/60Hz
S1 Close Relay Output 16A AC250V Volts free output
S2 Close Relay Output 10A AC250V Volts free output
Open Relay Output
10A AC250V Volts free output
LO Relay Output
16A AC250V Volts free output
NO Relay Output
16A AC250V Volts free output
Gen Start Relay
7A AC250V Volts free output
Communication
RS485 interface, MODBUS Protocol
Case Dimensions
139mmx120mmx50mm
Panel Cutout
130mmx111mm
Working Conditions
Temperature: (-25~+70)°C; Relative humidity: (20~93)%RH
Storage Condition
Temperature: (-30~+80)°C
Protection Level
IP65: when waterproof gasket is installed between controller and control
screen.
Insulation Strength
Apply AC1.5kV voltage between high voltage terminal and low voltage
terminal and the leakage current is not more than 3mA within 1min.
Weight
0.62kg