ACC7200 Air Compressor Controller User Manual Page 74 of 77
14.15
SCANIA
Suitable for S6 engine control module; Engine model is DC9, DC12, and DC16. Engine type: Scania.
Table 37 B1 Connector
Terminals of controller
B1 connector
Remark
Auxiliary Output 1
3
AUX. Output 1 is configured as “29: Fuel
Relay Output” (The configuration is factory
default).
Auxiliary Output 2
-
AUX. Output 2 is configured as “28:
Starting Relay Output” (The configuration
is factory default).
Connect to starter coil directly.
CAN(H)
9
Using impedance 120Ω connecting line.
CAN(L)
10
Using impedance 120Ω connecting line.
14.16
VOLVO EDC3
Suitable engine control mode is TAD1240, TAD1241, and TAD1242; Engine type: Volvo.
Table 38 “Stand alone” Connector
Terminals of controller
“Stand alone” connector
Remark
Auxiliary Output 1
H
AUX. Output 1 is configured as “29: Fuel
Relay Output” (The configuration is factory
default).
Auxiliary Output 2
E
AUX. Output 2 is configured as “28:
Starting Relay Output” (The configuration
is factory default).
Auxiliary output 3
P
AUX. Output 3 is configured as “36: ECU
Power;
Table 39 “Data Bus” Connector
Terminals of controller
“Data bus” connector
Remark
CAN(H)
1
Using impedance 120Ω connecting line.
CAN(L)
2
Using impedance 120Ω connecting line.
NOTE:
When this engine type is selected, preheating time should be set to at least 3 seconds.