ACC7200 Air Compressor Controller User Manual Page 62 of 77
9.10
CONTROLLER INFORMATION
This interface can display the development information of the controller, such as
software/hardware, release date.
10
SENSOR SETTING
If a sensor is needed to change again, the sensor curve will be transferred into the standard value. For
example, if the default temperature sensor is SGH(120ºC Resistance type) at default, the sensor curve
is SGH (120ºC Resistance type) curve; if it is set SGD, the temperature sensor curve is SGD curve.
If there is difference between standard sensor curve and the used sensor, users can choose “defined
sensor”, and input “defined sensor curve”.
If sensor is selected to “Not Used”, then sensor curve doesn't work.
If corresponding sensor only has alarm switch, then it is a must that set the sensor “Not Used”,
otherwise shutdown alarm or warning may occur.
It is applicable to set the headmost and backmost values in the vertical coordinate as the same as the
Figure 7.
Fig.7 Sensor Curve Setting