ACC4100 Diesel Air Compressor Controller User Manual Page 20 of 52
8
CONFIGURATION PARAMETER RANGE AND DEFINITION
8.1
PARAMETER RANGE AND DEFINITION
Table 9 Parameter Setting Contents and Range List
No.
Item
Range
Default
Description
Language
1
Language
(0-1)
0
0: Simplified Chinese 1: English
Override Mode
1
Override Mode
(0-1)
0
0: Disable 1: Enable
LCD Backlight
1
Contrast Ratio
(0-10)
5
Set LCD contrast ratio;
2
Brightness
(0-5)
5
Set LCD backlight brightness;
3
Delay
(0-3600)min
5
Backlight is always on when delay is set to
0min.
Module Setting
1
Module Address
(1-254)
1
Controller address for remote monitoring;
2
Comm. Stop Bit
(0-1)
0
0: 2-bit Stop Bit
1: 1-bit Stop Bit (PC software settings)
3
Password
(0-9999)
1234
It used for advanced parameter setting;
Caution!
Default password is “1234”; It can be
changed by operator for purpose of preventing
others
changing
controller
advanced
configuration.
If password is changed, please remember clearly.
If it is forgotten, please contact company service
person.
4
Date and Time
Users can calibrate date and time.
5
Maintain Password
(0-9999)
1234
Independent password for maintenance.
Timer Setting
1
Preheat Delay
(0-3600)s
0
Time for pre-heating plug to be energized
before starter is energized.
2
Prestart Fuel Time
(0-3600)s
1
Time for fuel relay output every time
before starter is energized.
3
Cranking Time
(3-60)s
8
Time for starter to be energized every
time.
4
Crank Rest Time
(3-60)s
10
Waiting time before second energization
when engine fails to start.
5
Safety On Delay
(0-3600)s
10
During this time oil pressure low, temp.
high, under speed, under frequency, under
voltage, and charge alt failure alarms are
all inactive.
6
Start Idle Time
(0-3600)s
10
Time for engine idle running in start
process.