![SMA SUNNY ISLAND SIC40-MPT Скачать руководство пользователя страница 39](http://html1.mh-extra.com/html/sma/sunny-island-sic40-mpt/sunny-island-sic40-mpt_technical-description_1294206039.webp)
SMA Solar Technology AG
Parameter Lists on the Sunny Island
Technical Description
SIC40-TEN081110
39
10.2 Events
Events describe state changes or transient states.
The meaning of events reported by the Sunny Island are explained in the following table:
10.3 Error (Warnings)
Errors describe impermissible or only limited permissible states. This includes warnings, failures and
errors. If an error or a failure is indicated by the illuminated red LED, contact your installer.
The meaning of warnings and errors reported by the Sunny Island are explained in the following
table:
Display no. Display text
Description
E851
Sic1Detect
First charge controller was detected
E852
Sic2Detect
Second charge controller was detected
E853
Sic3Detect
Third charge controller was detected
E854
Sic4Detect
Fourth charge controller was detected
Display no. Display text
Description
W851
Sic1BatShort
Pole of battery connection is reversed or short circuit on the first
charge controller
W852
Sic1BatVtgHi
Battery overvoltage (>65 V) on the first charge controller
W853
Sic1PvVtgHi
Overvoltage of PV generator on the first charge controller
W854
Sic1PvVtgLo
No PV voltage or short circuit on the first charge controller
W855
Sic1TmpLo
Sensor error or undertemperature on the first charge controller
W856
Sic1TmpHi
Device overtemperature on the first charge controller
W857
Sic1ComLoss
Communications loss on the first charge controller for more than
24 h
W861
Sic2BatShort
Pole of battery connection is reversed or short circuit on the
second charge controller
W862
Sic2BatVtgHi
Battery overvoltage (>65 V) on the second charge controller
W863
Sic2PvVtgHi
Overvoltage of PV generator on the second charge controller
W864
Sic2PvVtgLo
No PV voltage or short circuit on the second charge controller
W865
Sic2TmpLo
Sensor error or undertemperature on the second charge
controller
W866
Sic2TmpHi
Device overtemperature on the second charge controller
Содержание SUNNY ISLAND SIC40-MPT
Страница 1: ...Charge controller SUNNY ISLAND CHARGER Technical Description SIC40 TEN081110 98 2005210 Version 1 0 EN...
Страница 2: ......
Страница 6: ...SMA Solar Technology AG 6 SIC40 TEN081110 Technical Description...
Страница 48: ...Contact SMA Solar Technology AG 48 SIC40 TEN081110 Technical Description...
Страница 49: ...SMA Solar Technology AG Contact Technical Description SIC40 TEN081110 49...
Страница 50: ...Contact SMA Solar Technology AG 50 SIC40 TEN081110 Technical Description...