Battery Management
User Manual
SI3324/4248-14:FE2406
Page 39
6.3
Deep Discharge Protection / Battery State
When deeply discharged, lead acid batteries age 100 times more quickly than when
fully charged. Depending on the battery type, one speaks of deep discharge at
charge levels of less than 40 %. Reliable protection from deep discharge is essential
for a long battery service life. The Sunny Island 3324/4248 uses current-
compensated voltage thresholds combined with time delays for deep discharge
protection. The different levels, which can be easily set, are used to define the four
state of the batteries (BatState):
• Normal operation (BatState = Normal)
• 1st level (BatState = Warning)
• 2nd level (BatState = Low)
• 3rd level (BatState = Critical)
The following figure shows the four battery states:
As long as the Sunny Island 3324/4248 has not detected a deep discharge then it
is in the battery state (BatState) Normal.
As soon as the first level of deep discharge is reached, the Sunny Island 3324/4248
switches to the Warning state. This can be used to start a generator.
If the batteries are further discharged despite the warning, then the battery state now
jumps to the next deep discharge level Low. If desired, this level can be used to
trigger the Sunny Island 3324/4248 relay contact to switch off all or some of the
loads.
Normal
Warning
(Start
Generator)
Low
(Load
Shedding)
Critical
(Shut
down)
BatVoltage, BatCurrent >
SocLim1
for t > 15 minutes
BatVoltage, BatCurrent >
SocLim2
for t > 15 minutes
BatVoltage, BatCurrent >
SocLim3
for t > 15 minutes
or charge current
BatVoltage, BatCurrent <
SocLim1
for t > 2/6/30 minutes
BatVoltage, BatCurrent <
SocLim1
for t > 2/6/30 minutes
and no charging current
BatVoltage, BatCurrent <
SocLim2 for t > 2/6/30
minutes
100 %
SocLim1
SocLim2
SocLim3
0 %
Содержание Sunny Island 3324
Страница 1: ...Sunny Island 3324 4248 User Manual User Manual Version 4 0 SI3324 4248 14 FE2406 TBE SI4248 ...
Страница 2: ......
Страница 6: ...SMA Technologie AG Page 6 SI3324 4248 14 FE2406 User Manual ...
Страница 8: ...Notes on this Manual SMA Technologie AG Page 8 SI3324 4248 14 FE2406 User Manual ...
Страница 14: ...The Sunny Island 3324 4248 SMA Technologie AG Page 14 SI3324 4248 14 FE2406 User Manual ...
Страница 42: ...Frequency Shift Power Control FSPC SMA Technologie AG Page 42 SI3324 4248 14 FE2406 User Manual ...
Страница 44: ...Automatic Frequency Adjustment SMA Technologie AG Page 44 SI3324 4248 14 FE2406 User Manual ...
Страница 60: ...Troubleshooting Problem Solving SMA Technologie AG Page 60 SI3324 4248 14 FE2406 User Manual ...
Страница 64: ...CE Declaration of Conformity SMA Technologie AG Page 64 SI3324 4248 14 FE2406 User Manual ...
Страница 66: ...Contact SMA Technologie AG Page 66 SI3324 4248 14 FE2406 User Manual ...
Страница 75: ...SMA Technologie AG User Manual SI3324 4248 14 FE2406 Seite 75 ...
Страница 77: ......
Страница 78: ......
Страница 79: ......