6 Maintenance
SMA Solar Technology AG
Maintenance Manual
SCCP-JP-B1-WA-en-22
42
6.2
Maintenance Schedule and Consumables
6.2.1
Notes on Maintenance Work
Adverse ambient conditions reduce maintenance intervals
Location and ambient conditions influence the maintenance intervals. Note that cleaning and corrosion protection
may be required more frequently depending on the conditions at the installation site.
• If the DC subdistribution is subject to adverse ambient conditions, it is recommended to shorten the
maintenance intervals.
• SMA recommends an optical inspection every six months to determine the maintenance requirements.
Maintenance report for maintenance
All maintenance work must be documented in a maintenance report. The maintenance report can be found in the
download area at www.SMA-Solar.com.
Consumables and maintenance materials
Only those consumables and maintenance materials not normally included in the standard equipment of an
electrically qualified person are listed. It is taken for granted that standard tools and materials such as torque
wrenches, one-contact voltage testers and wrenches will be available for all maintenance operations.
Spare parts
Only original parts or parts recommended by SMA Solar Technology AG are to be used as spare parts when
replacing components.
Spare parts can be identified via the reference designation and the circuit diagram. The spare-parts list includes
the article numbers of each spare part. For information on a specific article number, contact us (see Section 9
"Contact", page 67).
6.2.2
Maintenance Work Every 24 Months
Required maintenance materials and tools:
☐ Vacuum cleaner
☐ A suitable water-free, heat-resistant lubricant
☐ A testing device approved by the manufacturer of the AC disconnection unit, e.g. TT1 by ABB
☐ Talcum, petroleum jelly or wax for maintaining the seals
☐ Use touch-up sticks, paint brushes, cans of spray paint or 2K-PUR acrylic paint in the appropriate RAL color to
repair small-area surface damage.
☐ Use touch-up paint or 2K-PUR acrylic paint in the appropriate RAL color to repair large-area surface damage.
☐ Abrasive cloth
☐ Degreaser
☐ A surge arrester testing device approved by the manufacturer of the surge arrester such as the PM20 by
DEHN + SÖHNE GmbH + Co. KG
Maintenance work depending on the condition of the inverter
Maintenance work with supply voltage present
Task
See
Reading off error messages and warnings
Checking the DC switchgear
Содержание Sunny Central 1000CP-JP
Страница 68: ...www SMA Solar com...