SMA
Technologie AG
Installation
Installation Guide
SB40TL_50TL-IEN081211
23
5.2.2 Mounting with a Top-Hat Rail
Requirements for mounting using top-hat rails
•
Use a TH-35-7.5 mounting rail compliant with DIN EN 60715.
•
Use stainless steel top hat rails and screws to prevent contact corrosion.
•
Mount on level surfaces only.
•
Use fastening material suitable for the surface only.
Take into account the weight of the Sunny Boy when selecting fastening materials.
Mounting procedure
1.
Use the top-hat rail as a drilling template and mark the positions of the drill holes.
2.
Secure the top-hat rail using suitable screws (at
least 6 mm in diameter) and washers (min. outer
diameter: 18 mm).
Secure one screw at least every 300 mm.
3.
Transport the Sunny Boy using the handles at the
sides of the Sunny Boy.
4.
Attach the Sunny Boy to the top-hat rail using the
mounting opening in the rear wall.