![SMA SUNNY BOY 1100 Скачать руководство пользователя страница 39](http://html1.mh-extra.com/html/sma/sunny-boy-1100/sunny-boy-1100_installation-manual_1294430039.webp)
SMA Solar Technology AG
Technical Data
Installation Guide
SB11_17-IEN084820
39
11 Technical Data
PV generator connection data
SB 1100
SB1700
Max. input voltage
U
DC max
400 V
a)
Input voltage, MPP range
U
PV
139 V ... 320 V
Max. input current
I
PV, max
10 A
12.6 A
Max. input power
P
DC
1210 W
1850 W
Recommended total generator power
1350 Wp
(for Central Europe)
2050 Wp
(for Central Europe)
Voltage ripple
U
PP
< 10 % of the input voltage
Internal consumption during operation
< 4 W (standby)
< 5 W (standby)
a) The maximum open circuit voltage, that can occur with - 10 °C cell temperature may not exceed the maximum
input voltage.
Grid connection data
SB 1100
SB 1700
Nominal output power
P
AC, nom
1000 W
1550 W
Peak output power
P
AC, max
1100 W
1700 W
Nominal output current
I
AC, nom
4.4 A
6.7 A
Max. output current
I
AC, max
5.6 A
8.6 A
Max. fuse protection
16 A
Harmonic distortion of output current
(at K
Ugrid
< 2 %, P
AC
> 0.5 P
ACnom
)
K
IAC
< 3 %
Short-circuit tolerance
grid-side via current regulation
Nominal operating voltage
U
AC, nom
220 V / 230 V / 240 V
Voltage range
(extended operating range)
U
AC
180 V ... 260 V
Nominal operating frequency
f
AC, nom
50 Hz / 60 Hz
Frequency range
(extended operating range)
f
AC
50 Hz: 45.5 Hz ... 54.5 Hz
60 Hz: 55.5 Hz ... 64.5 Hz
Power factor (at nominal output power)
cos phi
1
Overvoltage category
III
Test voltage (DC)
1.7 kV
(1 s routine testing / 5 s type testing)
Surge testing voltage
4 kV (serial interface: 6 kV)
Internal consumption in night operation
0.1 W