6 Mounting
SMA Solar Technology AG
Installation Manual
SCCP-JP_NR-IA-en-11
18
3. Fasten the grounding cable to the rear-panel bolt using a torque
wrench (AF 13, torque: 6 Nm).
4. Ensure that the grounding cable is correctly mounted.
5. Apply metal-free all-purpose paste to all threads and set screws.
6. Align the rear panel on the inverter and hook it into the hook fitting.
7. Insert the five upper screws of the rear panel into the threads and
tighten (TX 30, torque: 8 Nm).
5x
8. Make sure that the rear panel is correctly mounted.
6.6
Mounting the Kick Plate for the Sound Absorber
The kick plate must be mounted with an additional air duct on the rear side of the inverter.
Procedure:
1. Apply metal-free all-purpose paste to all threads in the base area.
2. Position and align the kick plate for the sound absorber on the
enclosure.
3. Screw the previously retained pan head flange screws into the threads.
4. Tighten the pan head flange screws on the kick plate (TX 30, torque: 8 Nm).
6.7
Mounting the Ventilation Plate
The guide rails for the ventilation plate are located in the floor area of the inverter cabinet.