485i-Module-IA-en-19 | Version 1.9

ENGLISH

Communication Interface for SMA Inverters

485 Data Module

Installation Manual

Содержание 485 Data Module

Страница 1: ...485i Module IA en 19 Version 1 9 ENGLISH Communication Interface for SMA Inverters 485 Data Module Installation Manual...

Страница 2: ...n if not explicitly identified as such Missing designations do not mean that a product or brand is not a registered trademark The BLUETOOTH word mark and logos are registered trademarks owned by Bluet...

Страница 3: ...ed in the Inverter 8 3 2 Order Option 485 Data Module as Retrofit Kit 8 4 Product Description 9 4 1 485 Data Module 9 4 2 Type Label 9 4 3 Cable Gland 10 5 Connection 11 5 1 Device Overview 11 5 2 Ins...

Страница 4: ...ocument see Section 2 2 Skills of Qualified Persons page 7 Symbols Symbol Explanation Indicates a hazardous situation which if not avoided will result in death or serious injury Indicates a hazardous...

Страница 5: ...lay texts Elements on a user interface Terminals Elements to be selected Elements to be entered The value can be found in the field Energy Select Settings Enter the value 10 in the field Minutes Conne...

Страница 6: ...Technology AG for this product Only use the 485 Data Module in accordance with the information provided in the enclosed documentation Any other use can result in personal injury or property damage The...

Страница 7: ...ock Lethal voltages are present in the conductive parts of the inverter Prior to performing any work on the inverter disconnect the inverter from all voltage sources on the AC and DC sides see inverte...

Страница 8: ...3 2 Order Option 485 Data Module as Retrofit Kit Check the delivery for completeness and any visible external damage Contact your distributor if the delivery is incomplete or damaged Figure 2 Compone...

Страница 9: ...tion for SMA inverters Figure 3 Design of the 485 Data Module 4 2 Type Label The type label clearly identifies the 485 Data Module The type label is located at the bottom right on the back of the 485...

Страница 10: ...le gland provides a sturdy tightly sealed connection of the cables to the inverter enclosure The cable gland also protects the inverter from dust and moisture intrusion Figure 5 Product description Ca...

Страница 11: ...5 Connection 5 1 Device Overview Figure 6 Overview of the connection area Position Designation A Flipped up display with screw B Cable route to the plugs of the 485 Data Module C Inverter enclosure op...

Страница 12: ...the display up until it snaps into place 4 Push the pre mounted filler plug out of the second hole from the left in the inverter enclosure 5 Attach the cable gland to the enclosure opening using the c...

Страница 13: ...h the ribbon cable upwards behind the display The key on the top edge of the 485 Data Module must fit into the hole in the plastic retainer in the inverter 7 485 Data Module hand tight using a hexagon...

Страница 14: ...e end of the cable which is to be connected to the 485 Data Module 2 Shorten the cable shield to 15 mm 3 Fold the surplus cable shield back over the cable sheath 4 Wrap the cable shield in conductive...

Страница 15: ...inverter 3 Press the seal out of the cable gland from the inside 4 Route the cable from the outside into the inverter through the unfastened swivel nut and the cable gland 5 Remove one of the filler p...

Страница 16: ...onnected in terminals 2 and 7 10 Open the spring clamp terminals on the plug 11 Connect the insulated conductors to the plug terminals and note down the color of the insulated conductors The allocatio...

Страница 17: ...he cable gland hand tight This relieves pull strains on the cables 15 Flip the display down and fasten the screw of the display hand tight 16 Close the inverter see inverter installation manual 17 Con...

Страница 18: ...ule 7 Remove the cables from the 485 Data Module 8 Unscrew the counter nut of the cable gland 9 Pull the cable gland and cables out of the inverter 10 Release the screw of the 485 Data Module and remo...

Страница 19: ...r packaging that is suitable for the weight and size of the 485 Data Module 6 3 Disposing of the 485 Data Module Dispose of the 485 Data Module in accordance with the regulations for the disposal of e...

Страница 20: ...inverter from all voltage sources on the AC and DC sides see inverter installation manual Several SMA communication products are simultaneously querying data from the devices via Bluetooth e g Sunny E...

Страница 21: ...Width x height x depth 73 mm x 88 mm x 34 mm Weight 71 g Communication interface RS485 Maximum cable length 1200 m Type of plug 4 pole spring cage terminal Number of RS485 connections 2 Ambient temper...

Страница 22: ...9 Monitoring Systems Kommunikationsprodukte 49 561 9522 2499 Fuel Save Controller PV Diesel Hybridsysteme 49 561 9522 3199 Sunny Island Sunny Backup Hydro Boy 49 561 9522 399 Sunny Central 49 561 9522...

Страница 23: ...ar Technology South Africa Pty Ltd Cape Town 08600SUNNY 08600 78669 International 27 0 21 826 0600 Argentina Brasil Chile Per SMA South America SPA Santiago 562 2820 2101 Australia SMA Australia Pty L...

Страница 24: ...www SMA Solar com SMA Solar Technology...