22
E95.1901EN032 User manual Slant Fin VGH-CH / CO
Boiler history
The last 15 lockouts and 15 blocking errors are stored in the boiler control. This boiler history can be shown via the
Boiler History screen via the installer boiler status menu in one of the advanced displays.
•
Successful ignitions
•
Failed Ignitions
•
Flame Failures
•
Operation days
•
CH Burner Hours
•
DHW Burner Hours
Lockout codes
If you cannot restart your boiler with the reset button, contact your installer.
Maintenance and repairs must be carried out by a certified technician/installer.
Lock
out
code
Error
Description
Cause
Solving
0
E2PROM_READ
_ERROR
Internal software error
wrongly programmed
BCU or PB
If the boiler does not start
after Reset, contact your
installer
1
IGNIT_ERROR
Five unsuccessful ignition
attempts in a row
no gas, wrongly
adjusted gas valve
If the boiler does not start
after Reset, contact your
installer
2
GV_RELAY_
ERROR
Failure detected in the
gas valve relay
short circuit in coil of
the gas valve, water
on wiring or gas
valve
If the boiler does not start
after Reset, contact your
installer
3
SAFETY_RELAY
_ERROR
Failure detected in safety
relay
safety relay is not
working correctly
If the boiler does not start
after Reset, contact your
installer
4
BLOCKING_
TOO_LONG
Control had a blocking
error for more than 20
hours
blocking code active
for more than 20
hours
Reset and check blocking
code
5
FAN_ERROR_
NOT_RUNNING
Fan is not running for
more than 60 seconds
electrical wiring not
correctly connected,
or fan is
malfunctioning
If the boiler does not start
after Reset, contact your
installer
6
FAN_ERROR_
TOO_SLOW
Fan runs too slow for
more than 60 seconds
electrical wiring not
correctly connected,
or fan is
malfunctioning
If the boiler does not start
after Reset, contact your
installer
7
FAN_ERROR_
TOO_FAST
Fan runs too fast for more
than 60 seconds
electrical wiring not
correctly connected,
or fan is
malfunctioning
If the boiler does not start
after Reset, contact your
installer
8
RAM_ERROR
Internal software error
wrongly programmed
BCU or PB
If the boiler does not start
after Reset, contact your
installer
9
WRONG_
EEPROM_
SIGNATURE
Contents of E2prom is not
up to date
out dated E2prom
If the boiler does not start
after Reset, contact your
installer
10
E2PROM_
ERROR
Wrong safety parameters
in E2prom
wrongly programmed
BCU or PB
If the boiler does not start
after Reset, contact your
installer
11
STATE_ERROR
Internal software error
wrongly programmed
BCU or PB
If the boiler does not start
after Reset, contact your
installer
WARNING
Содержание VGH-100-CH
Страница 2: ......
Страница 5: ...5 E95 1901EN032 User manual Slant Fin VGH CH CO 1 SAFETY GUIDELINES...
Страница 6: ...6 E95 1901EN032 User manual Slant Fin VGH CH CO CONSIGNES DE S CURIT...
Страница 28: ...28 E95 1901EN032 User manual Slant Fin VGH CH CO...
Страница 29: ......
Страница 30: ......
Страница 31: ......