E95.1901EN032 User manual Slant Fin VGH-CH / CO 

 

   Boiler history 

The last 15 lockouts and 15 blocking errors are stored in the boiler control. This boiler history can be shown via the 
Boiler History screen via the installer boiler status menu in one of the advanced displays. 

 

 

 

Successful ignitions  

 

Failed Ignitions  

 

Flame Failures 

 

Operation days 

 

CH Burner Hours 

 

DHW Burner Hours 

 

   Lockout codes 

 

If you cannot restart your boiler with the reset button, contact your installer. 
Maintenance and repairs must be carried out by a certified technician/installer. 

 

Lock
out 
code 

Error 

Description 

Cause 

Solving 

E2PROM_READ
_ERROR 

Internal software error 

wrongly programmed 
BCU or PB 

If the boiler does not start 
after Reset, contact your 
installer 

IGNIT_ERROR 

Five unsuccessful ignition 
attempts in a row 

no gas, wrongly 
adjusted gas valve  

If the boiler does not start 
after Reset, contact your 
installer 

GV_RELAY_ 
ERROR 

Failure detected in the 
gas valve relay 

short circuit in coil of 
the gas valve, water 
on wiring or gas 
valve  

If the boiler does not start 
after Reset, contact your 
installer 

SAFETY_RELAY
_ERROR 

Failure detected in safety 
relay 

safety relay is not 
working correctly 

If the boiler does not start 
after Reset, contact your 
installer 

BLOCKING_ 
TOO_LONG 

Control had a blocking 
error for more than 20 
hours 

blocking code active 
for more than 20 
hours 

Reset and check blocking 
code 

FAN_ERROR_ 
NOT_RUNNING 

Fan is not running for 
more than 60 seconds 

electrical wiring not 
correctly connected, 
or fan is 
malfunctioning 

If the boiler does not start 
after Reset, contact your 
installer 

FAN_ERROR_ 
TOO_SLOW 

Fan runs too slow for 
more than 60 seconds 

electrical wiring not 
correctly connected, 
or fan is 
malfunctioning 

If the boiler does not start 
after Reset, contact your 
installer 

FAN_ERROR_ 
TOO_FAST 

Fan runs too fast for more 
than 60 seconds 

electrical wiring not 
correctly connected, 
or fan is 
malfunctioning 

If the boiler does not start 
after Reset, contact your 
installer 

RAM_ERROR 

Internal software error 

wrongly programmed 
BCU or PB 

If the boiler does not start 
after Reset, contact your 
installer 

WRONG_ 
EEPROM_ 
SIGNATURE 

Contents of E2prom is not 
up to date 

out dated E2prom  

If the boiler does not start 
after Reset, contact your 
installer 

10 

E2PROM_ 
ERROR 

Wrong safety parameters 
in E2prom 

wrongly programmed 
BCU or PB 

If the boiler does not start 
after Reset, contact your 
installer 

11 

STATE_ERROR 

Internal software error 

wrongly programmed 
BCU or PB 

If the boiler does not start 
after Reset, contact your 
installer 

  

   

 

WARNING

 

Содержание VGH-100-CH

Страница 1: ...WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follo...

Страница 2: ......

Страница 3: ...R BOILER 11 FUNCTIONAL INTRODUCTION 11 INSTALLATION AND SETTINGS 11 4 DISPLAY AND BUTTONS 12 DISPLAY ICONS 12 SCREENS AND SETTINGS 13 De aeration sequence 13 CONTROL PANEL MENU STRUCTURE 14 Set Actual...

Страница 4: ...y Alert Symbol indicates a hazardous situation which will or can cause minor or moderate personal injury or property damage Caution Sign plus a lightning bolt indicates the risk of electric shock and...

Страница 5: ...5 E95 1901EN032 User manual Slant Fin VGH CH CO 1 SAFETY GUIDELINES...

Страница 6: ...6 E95 1901EN032 User manual Slant Fin VGH CH CO CONSIGNES DE S CURIT...

Страница 7: ...ead and follow the supplied instructions before installing servicing or removing this boiler This boiler contains materials that have been identified as carcinogenic or possibly carcinogenic to humans...

Страница 8: ...pressure BCU Burner Control Unit BTU British Thermal Unit C Degree Celsius CH Central Heating Heating Only CO 1 Combi boiler CH DHW 2 Carbon monoxide CO2 Carbon dioxide Combi A boiler providing a comb...

Страница 9: ...ebris Inspect also for any gaps at the wall penetration s which could allow vented gasses to reenter the home Visually inspect water and gas pipes for leaks Visually inspect to see that the condensate...

Страница 10: ...ent terminal The plate must be of sufficient size to be easily read from a distance of eight feet away and read Gas Vent Directly Below For direct vent boilers mechanical vent heating boilers or domes...

Страница 11: ...thermostat control CH mode 2 Central Heating with full outdoor temperature reset CH mode 3 Central Heating with permanent heat demand CH mode 4 Central Heating with analog input control of setpoint C...

Страница 12: ...nt LEFT Return to previous menu item or Status overview UP Directly select Actual setpoint of DHW setpoint in the Status overview push RIGHT to confirm and use UP or DOWN to adjust value DOWN Directly...

Страница 13: ...ATION SEQUENCE The De Aeration sequence is a safety function that starts at every power ON of the boiler and is used to remove the air from the heat exchanger The DAir sequence does not start after a...

Страница 14: ...owing service intervals Using the submenu s following items can be set 1 Language To set the menu language 2 Unit Type Setting to imperial or SI units 3 Date Time Set date time zone display mode summe...

Страница 15: ...The header in the display shows you are inside the main menu While scrolling through the menu you will see that the selected menu item is shown in a white rectangle Enter a menu item by pressing ENTER...

Страница 16: ...and Italian BE AWARE DO NOT set the language to the Chinese Language if you are not familiar with this language Contact your installer for instructions if the display is set to Chinese and needs to b...

Страница 17: ...104 40 F C Installer Set CH setpoint when outdoor temperature equals Bas Outd T WW Shutdown 32 0 95 35 72 22 F C Installer Set outdoor temperature above which CH demand is locked Bas Outd T 32 0 86 3...

Страница 18: ...Calculated Setpoint F C User Actual CH setpoint 3 3 Boiler history min max Default unit Access level Description Successful Ignitions User Display the number of successful ignitions Failed Ignitions...

Страница 19: ...cess level Description Date dd mm yy User Set the current date Time hh mm User Set the current time A Time Zone Settings User Enter the time zone settings menu B Display Settings User Enter the displa...

Страница 20: ...the freezing of the Central Heating circuit when the boiler is in error during the winter period For some non volatile lockouts the circulator will not be running also see the error tables in this cha...

Страница 21: ...only Filter errors based on Boiler ID Managing Dep 1 Dep2 etc Clear Error Log Clear the error log protected by password When no filtering option is selected Disabled the error log will show all errors...

Страница 22: ...ctly If the boiler does not start after Reset contact your installer 4 BLOCKING_ TOO_LONG Control had a blocking error for more than 20 hours blocking code active for more than 20 hours Reset and chec...

Страница 23: ...the heat exchanger or flue gas sensor is malfunctioning or heat exchanger is overheated If the boiler does not start after Reset contact your installer 17 STACK_ERROR Internal software error wrongly p...

Страница 24: ...CHANGE_ DIFF_ERROR The 2 exchange sensors deviate too much for more than 60 seconds there is not enough water flow through the heat exchanger If the boiler does not start after Reset contact your inst...

Страница 25: ...boiler does not start after Reset contact your installer 107 REFHI_TOO_ LOW Internal hardware error wrongly programmed BCU or PB If the boiler does not start after Reset contact your installer 108 REF...

Страница 26: ...unctioning DHW sensor or short circuiting If the boiler does not start after Reset contact your installer 130 FLUE_ SHORTED Flue sensor shorted malfunctioning flue sensor or short circuiting If the bo...

Страница 27: ...ade control lost communication with one of the depending connection between cascaded boilers is interrupted or wiring is broken Contact your installer 202 APP_SELECTION_ ERROR Unknown appliance model...

Страница 28: ...28 E95 1901EN032 User manual Slant Fin VGH CH CO...

Страница 29: ......

Страница 30: ......

Страница 31: ......

Страница 32: ...UBLICATIONVGHR UIM SLANT FIN CORPORATION Greenvale N Y 11548 Phone 516 484 2600 FAX 516 484 5921 Canada Slant Fin LTD LTEE Mississauga Ontario 400 Ambassador Drive Mississauga Ontario L5T 2J3Phone 905...

Отзывы: