The following safety labels are found on the right side of the power packs:
Figure 2.
Power pack lead safety labels.
Safety precautions
Read and follow all safety precautions and safe operating practices in your manual. Do not
exceed maximum operating capabilities of the Baker AWA-IV tester, power packs, or the
Baker ZTX accessory.
The general safety information presented here is for both operating and service personnel.
You will find specific warnings and cautions throughout this manual where they apply.
If using the equipment in any manner not specified by SKF USA, Inc. the protection provided
by the equipment may be impaired.
WARNING
Failure to heed the following safety precautions can result in injury or
death from severe electrical shock.
Test related
• Two-party operation is recommended only when using proper equipment (such as
the remote E-Stop) and when taking appropriate precautions so both operators are
aware of all conditions at all times.
• Always know what test is being performed and when. For example,
do not
adjust
test leads when operating a footswitch. Leads will have live voltage and severe
electrical shock may result.
• For capacitor-started motors or systems with surge arrestors/power factor
capacitors, be sure to
disconnect
all capacitors from the test circuit
before
testing.
• Upon completion of any DC-HiPot, megohm, polarization index (PI), step voltage, or
dielectric absorption (DA) tests, be sure to short the winding to ground and allow
time for discharge before disconnecting the test leads. If you do not do this, voltage
may build up on the winding. A common approach is to allow a winding to discharge
four times the total amount of time that DC voltage is applied to the winding.
• If the tester is removed from the windings before complete discharge, short winding
leads together and ground them using appropriate jumper cables.
• Make sure to disconnect the tester leads before energizing or powering up the
motor.
4
PUB CM/I4 71-015 EN V13.2 Static Motor Analyzer—Baker AWA-IV User Manual
Safety and general operating information
Содержание Baker AWA-IV 12 HO
Страница 1: ...SKF Static Motor Analyzer Baker AWA IV User manual...
Страница 2: ......
Страница 22: ...2 PUB CM I4 71 015 EN V13 2 Static Motor Analyzer Baker AWA IV User Manual About this manual...
Страница 126: ...106 PUB CM I4 71 015 EN V13 2 Static Motor Analyzer Baker AWA IV User Manual Test procedures...
Страница 202: ...182 PUB CM I4 71 015 EN V13 2 Static Motor Analyzer Baker AWA IV User Manual Database definition...
Страница 206: ...186 PUB CM I4 71 015 EN V13 2 Static Motor Analyzer Baker AWA IV User Manual...
Страница 213: ......