44
Document NO.: RD-690-39-001 Version: A Date
:
2017.12.30
signal. In this case, Disabled audio/visual alarm devices will also be activated.
4.3.9.1.2
Operation
1)
By pressing the
【
1
】
key from the General screen enters into the Two Dev-Evacuate mode.
2)
Press the
【
UP
】
and
【
DOWN
】
key to select DISABLED or ENABLED.
3)
Press
【
ENTER
】
key to confirm the selection.
4)
Press
【
MENU
】
key to return to previous menu.
4.3.9.2 Call Point Evacuate (Menu Item 7-2-2)
4.3.9.2.1
Description
The activation of any manual call point can be configured to activate evacuation. In this case, Disabled audio/visual
alarm devices will also be activated.
4.3.9.2.2
Operation
1)
By pressing the
【
2
】
key from the General screen enters into the Call Point Evacuate mode.
2)
Press the
【
UP
】
and
【
DOWN
】
key to select DISABLED or ENABLED.
3)
Press
【
ENTER
】
key to confirm the selection.
4)
Press
【
MENU
】
key to return to previous menu.
4.3.9.3 NAC Status (Menu Item 7-2-3)
4.3.9.3.1
Description
The status of Notification Appliances Circuits (NACs) can be configured to DISABLED or ENABLED. The type of
NACs can be set to CONTINUE, PULSE or STOP. The NACs will not output when setting the STOP type.
Disabled NACs will be indicated on the LCD and can be reviewed using
【
DISABLED
】
key.
4.3.9.3.2
Operation
1)
By pressing the
【
3
】
key from the General screen enters into the NAC Status mode.
2)
Press the direction keys to select status and type of NACs.
3)
Press
【
ENTER
】
key to confirm the selection and it will automatically to return the previous menu.
4.3.10
Other Features
4.3.10.1
System Mode (Menu Item 7-3-1)
4.3.10.1.1 Description
The mode of the system can be set to Active or Installation mode.
Installation mode is used during installation and commissioning. In Installation mode, the
equipment scans for
changes or new devices on the loop. The SYSTEM ON LED will flash under this mode. Where changes to existing
DD/MM/YY <Panel Status> HH:MM:SS
1. System Mode 4.User Authority
2. User Code 5.Restore Factory Settings
3. Admin Code 6.Communication [ General]
Содержание GS690
Страница 18: ...18 Document NO RD 690 39 001 Version A Date 2017 12 30 Figure 11 Figure 12 ...
Страница 27: ...27 Document NO RD 690 39 001 Version A Date 2017 12 30 ...
Страница 29: ...29 Document NO RD 690 39 001 Version A Date 2017 12 30 ...
Страница 30: ...30 Document NO RD 690 39 001 Version A Date 2017 12 30 ...
Страница 31: ...31 Document NO RD 690 39 001 Version A Date 2017 12 30 ...