3.6.5 Addressable Loops
Figure
–24
Class A Style
Figure
–25
Class B Style
Each loop has capacity for 127 addressable devices.
There are two ways of circuit wiring, It is suggested that A should be adopted.If the loops is not correctly installed
(outgoing and incoming connections)the control and indicating equipment will not be able to monitor open-and
short-circuit conditions of the wiring.
Wiring for the addressable loops should use 2-core shielded cable with a cross-sectional area of (0.5~2.5)mm. Each
loop requires a separate shielded cable. wiring for non-addressable devices should not be contained within the shielded
addressable loop wiring.
Run the wiring as a loop, from the OUT terminals, to the field devices, and back to the RET terminals. connect the