sisel ENDA ERFA1-NTC-240 Series Скачать руководство пользователя страница 1

 

INPUT

NTC sensor

Input
Measutement range

SİSEL MÜHENDİSLİK ELEKTRONİK SAN. VE TİC. A.Ş.

Şerifali Mah. Barbaros Cad. No:18 Y.Dudullu  34775
ÜMRANİYE/İSTANBUL
Tel : +90 216 499 46 64 Pbx.    Fax : +90 216 365 74 01
url : www.enda.com.tr

1/2

ENDA

TM

ERFA1-NTC-240-EN-02-210317

40A AC Load current.
180-280V AC Load voltage.
NTC Sensor input.
0-95°C measurement range. 
4 Digits LED display.
Adjustable SET value between 0 and 60°C.
Adjustable hysteresis value between 3 and 31°C.
Adjustable minimum output value between %0 and %100.
Phase angel controlled.
Varistor protection for peak voltages.
CE Marked according to European Norms.

ERF  A  1 - NTC - 2  40 

ERF

A

1

NTC

SET

ERFA

Single - Phase

Fan Speed Controller 

END

A

SET

40

2

Input

NTC sensor

0 - 95°C

PSC

 message will flash on display and the output will be 100% if the sensor or the line short-circuit.

PFA

 message will flash on display and the output will be 100% if the sensor or the line open-circuit.

Protection

ENVIRONMENTAL CONDITIONS

-

25... +60 °C / -30... +100 °C (Shouldn't be icing and condensation in ambient.)

50% Relative humidity for +40°C temperature increases up to 90% at +20°C. (Shouldn't be condensation)
2
II
Max. 1000m
IP20 According to EN60529
 

Ambient/storage temperature
Relative humidity
Pollution degree
Overvoltage category
Altitude
Protection

OUTPUT

 

 

 

ERFA1-240 

40
180 - 280
150
400
1,6
5
880
50 - 60

>

0,75

160

Order code
Load Current, AC51/25?C (Arms)
Load voltage (Vrms)
Overload current t=1s/25°C (Arms)
Non rep.surge current/25°C (Arms)
On-state voltage drop (Vrms)
Leakage current (mArms)
I²t for fusing t=10ms (A²s)
Frequency (Hz)
Power factor (CosΦ)
Minimum operating current (mArms)

ENDA ERFA1-NTC-240 SERIES NTC SENSOR INPUT FAN SPEED CONTROLLER

ORDER CODE : 

Product Base Code

Fan Speed Control

Load Current

40A AC

Load Voltage

AC

Number of Pole

Single Pole

Please read this document carefully before using this product. The guarantee will be invalidated if the device is damaged 
by not following instructions detailed in the manual. The company shall not be responsible for any damage or losses 
however caused, which may be experienced as a result of the installation or use of this product.  

Thank you for choosing 

ENDA ERFA1-NTC-240

 Series fan speed controller devices.

2500 Vrms between I/O terminals for 1 min.
For power line 16mm² cable (with 25mm² cable terminal) cable, for signal line can be connected 4mm² cable.
Max. 1,2Nm

Self extinguishing plastics (According to EN 60695-11-10 V-O)

Load Voltage

180-280V AC

ERFA1-NTC-240

W46xH100xD120mm

450g

EN 60947-4-3
Rail mount (EN60715,TH35)

GENERAL

Dimensions                                                 

 

Weight

Order code                                                 

Isolation Voltage
Connection

Terminal screw torque
Product standard

 Mo

unting

 

Enclosure material

KEEP AWAY device from exposed to corrosive, volatile and flammable gases or liquids and
DO NOT USE the device in similar hazardous locations.

Avoid any liquid contact while the device is switched on.
DO NOT clean the device with solvent (thinner, gasoline, acid etc.) and / or abrasive cleaning agents.

Отзывы: