3. Technical parameters of Xroom units
1.
Basic technical parameters
-
Basic technical parameters – Xroom-100 (XR1-010-ECxxHR...) – heat exchanger
14
Version 1 – GBR(23/06/2021)
D-502-0152
-
Basic technical parameters – Xroom-100 (XR1-010-ECxxER...) – enthalpy exchanger
-
Basic technical parameters – Xroom-250 (XR1-025-ECxxHR...) – heat exchanger
Line
XR1-010-ECS0HRX… XR1-010-ECV1HRX… XR1-010-ECE1HRX… XR1-010-ECS0HRP… XR1-010-ECV1HRP… XR1-010-ECE1HRP…
Type of recovery exchanger
HRV with temperature efficiency
Unit equipment
pre-heater
-
-
-
electric
electric
electric
after heater
-
water
electric
-
water
electric
Nominal airflow/ BOOST*
m3/h
100/215
Heat output (range) of heating**
kW
-
0.33 - 1.38
0,5
-
0.33 - 1.38
0,5
Noise level**
dB(A)
32,1
Weight****
kg
16,3
18,3
19,3
16,8
18,8
19,8
Water volume in exchanger
l
-
0,51
-
-
0,51
-
Power supply of the unit
V/Hz
1 ~ 230/ 50-60
Nominal input power of the unit/
W
30/167
30/167
530/667
300/437
300/437
800/937
Nominal current of the unit /BOOST*
A
0.3/1.32
0.3/1.32
2.5/3.5
1.5/2.5
1.5/2.5
3.7/4.7
Recovery efficiency
per EN 308
heat
%
up to 87
humidity
%
-
-
-
-
-
-
Protection type
IP
20
Energy efficiency class (ERP)
cold climate A+, medium climate A, warm climate A
* BOOST mode - intensive ventilation for 10minutes
** at the temperature gradient of 75/60and an inlet air temperature of 20°C
*** Sound pressure level in free space at a distance of 3 m
**** unit weight, without water and packaging
Line
XR1-010-ECS0ERX… XR1-010-ECV1ERX… XR1-010-ECE1ERX… XR1-010-ECS0ERP… XR1-010-ECV1ERP… XR1-010-ECE1ERP…
Type of recovery exchanger
ERV with temperature and humidity efficiency
Unit equipment
pre-heater
-
-
-
electric
electric
electric
after heater
-
water
electric
-
water
electric
Nominal airflow/ BOOST*
m3/h
90/205
Heat output (range) of heating**
kW
-
0.29 - 1.24
0,5
-
0.29 - 1.24
0,5
Noise level**
dB(A)
32,1
Weight****
kg
16,3
18,3
19,3
16,8
18,8
19,8
Water volume in exchanger
l
-
0,51
-
-
0,51
-
Power supply of theunit
V/Hz
1 ~ 230 / 50-60
Nominal input power of the unit /
W
30/167
30/167
530/667
300/437
300/437
800/937
Nominal current of the unit / BOOST*
A
0.3/1.32
0.3/1.32
2.5/3.5
1.5/2.5
1.5/2.5
3.7/4.7
Recovery efficiency
per EN 308
heat
%
up to 90
humidity
%
up to 85
Protection type
IP
20
Energy efficiency class (ERP)
cold climate A+, medium climate A, warm climate B
* BOOST mode - intensive ventilation for 10 minutes
** at the temperature gradient of 75/60and an inlet air temperature of 20 °C
*** Sound pressure level in free space at a distance of 3 m
**** unit weight, without water and packaging
Line
XR1-025-ECS0HRX… XR1-025-ECV1HRX… XR1-025-ECE1HRX… XR1-025-ECS0HRP… XR1-025-ECV1HRP… XR1-025-ECE1HRP…
Type of recovery exchanger
HRV with temperature efficiency
Unit equipment
pre-heater
-
-
-
electric
electric
electric
after heater
-
water
electric
-
water
electric
Nominal airflow/ BOOST*
m3/h
250/350
Heat output (range) of heating**
kW
-
1.34 - 3.49
1
-
1.34 - 3.49
1
Noise level**
dB(A)
32,6
Weight****
kg
36
39,4
41,2
37
40,4
42,2
Water volume in exchanger
l
-
1,17
-
-
1,17
-
Power supply of theunit
V/Hz
1 ~ 230 / 50-60
Nominal input power of the unit /
W
61/169
61/169
1061/1169
479/709
480/709
1480/1709
Nominal current of the unit / BOOST*
A
0.61/1.42
0.61/1.42
5/5.8
3/3.8
3/3.8
7.3/8.2
Recovery efficiency
per EN 308
heat
%
up to 87
humidity
%
-
-
-
-
-
-
Protection type
IP
20
Energy efficiency class (ERP)
cold climate A+, medium climate A, warm climate B
* BOOST mode - intensive ventilation for 10 minutes
** at the temperature gradient of 75/60 and an inlet air temperature of 20 °C
*** Sound pressure level in free space at a distance of 3 m
**** unit weight, without water and packaging
Tab 1
Tab 2
Tab 3
Содержание XROOM
Страница 10: ...Fig 2 8 9 13 14 10 11 12 15 16 17 19 19 23 10 Version 1 GBR 23 06 2021 D 502 0152...
Страница 19: ...1 2 3 4 5 6 7 19 Version 1 GBR 23 06 2021 D 502 0152 Fig 5...
Страница 40: ...5 4 2 Description of the functions of the buttons and regulation Tab17 40 Version 1 GBR 23 06 2021 D 502 0152...