User Manual of EM730/EM730E Series Inverter
174
Valid delay
Function i
output
Level output
Invalid delay
Pulse output width
Single pulse output
Valid
Invalid
Valid
Invalid
Valid
Invalid
Fig. 7-15 Schematic Diagram of Level and Single Pulse Output of Digital Output Terminal
When the status of the selected function changes, the corresponding output terminal will
make a response with delay based on the function code settings. At present, the terminals Y1 and
R1 support this function. Details under default conditions: When the function changes from the
invalid to valid status and is maintained with the valid delay, the corresponding output terminal
will output the active level. When the function changes from the valid to invalid status and is
maintained with the invalid delay, the corresponding output terminal will output the inactive
level.
★
If the function code is set to 0.000s, the delay will be invalid.
Function
code
Function code name
Parameter description
Unit
Default
setting
Attribute
F03.17
Single pulse time of
Y1 output
0.001 - 30.000
s
0.250
●
F03.19
Single pulse time of
R1 output
0.001 - 30.000
s
0.250
●
When one function output terminal is in the single pulse output mode (see F03.05 for
details), the pulse width of the active level can be controlled by setting the single pulse output
time, in order to meet different process or control requirements. Details are given in Fig. 7- and